ELE02-01311
| Final | 6/25/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 06/25/2002 at 15:09:59. Contact: ###-####. no access they will reschedule 6/27/2002 11:30:41 AM
|
ELE02-01533
| Final | 6/26/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 06/26/2002 at 12:07:21. Contact: ###-####. ok card signed 6/27/2002 10:37:47 AM
|
ELE02-01938
| Temporary Service | 6/26/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 06/26/2002 at 14:27:35. Contact: ###-####.
t/s u/g new ok 6/27/2002 12:05:59 PM
|
ELE02-01943
| Electrical Rough-In | 6/26/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | A | PASS |
|
|
alan- ###-####-key is under rock on right hand side of front door walls S E corner of building 6/27/2002 10:13:22 AM
|
ELE02-01973
| Electrical Rough-In | 6/26/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | A | PART |
|
|
###-#### walls 6/27/2002 11:13:31 AM
|
ELE02-01767
| Electrical Rough-In | 6/27/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 06/27/2002 at 09:07:56. Contact: ###-####. r/i for paddle fans and fire alarm ok 6/27/2002 4:56:38 PM
|
ELE02-01979
| Electrical Rough-In | 6/27/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | P | PART |
|
|
r/i- bill ###-#### or ###-####?? conference only ok 6/27/2002 2:58:30 PM
|
ELE02-01586
| Electrical Rough-In | 6/26/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | P | PART |
|
|
JESSIE ###-#### r/i for concrete encased electrode ok 6/27/2002 3:12:48 PM
|
ELE01-04209
| Final | 6/26/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | P | NR |
|
|
###-#### not ready 6/27/2002 5:29:35 PM
|
ELE02-01946
| Rough-In Permanent Service | 6/26/2002 | 6/27/2002 | 6/27/2002 12:00:00 AM | P | FAIL |
|
|
###-#### cor. posted met with contractor250.66 needs #4 GEC 250.52(A)(1) terminate GEC within 5 ft of where u/g enters,250.53(D)(2) needs 2 grd rods ,230.24(A) needs 8 ft over roof 6/27/2002 3:48:16 PM
|