Inspections for the day of: Thursday, June 27, 2002.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-01311 Final6/25/20026/27/20026/27/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 06/25/2002 at 15:09:59. Contact: ###-####. no access they will reschedule 6/27/2002 11:30:41 AM
ELE02-01533 Final6/26/20026/27/20026/27/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 06/26/2002 at 12:07:21. Contact: ###-####. ok card signed 6/27/2002 10:37:47 AM
ELE02-01938 Temporary Service6/26/20026/27/20026/27/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 06/26/2002 at 14:27:35. Contact: ###-####.

t/s u/g new ok 6/27/2002 12:05:59 PM
ELE02-01943 Electrical Rough-In6/26/20026/27/20026/27/2002 12:00:00 AMAPASS
alan- ###-####-key is under rock on right hand side of front door walls S E corner of building 6/27/2002 10:13:22 AM
ELE02-01973 Electrical Rough-In6/26/20026/27/20026/27/2002 12:00:00 AMAPART
###-#### walls 6/27/2002 11:13:31 AM
ELE02-01767 Electrical Rough-In6/27/20026/27/20026/27/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 06/27/2002 at 09:07:56. Contact: ###-####. r/i for paddle fans and fire alarm ok 6/27/2002 4:56:38 PM
ELE02-01979 Electrical Rough-In6/27/20026/27/20026/27/2002 12:00:00 AMPPART
r/i- bill ###-#### or ###-####?? conference only ok 6/27/2002 2:58:30 PM
ELE02-01586 Electrical Rough-In6/26/20026/27/20026/27/2002 12:00:00 AMPPART
JESSIE ###-#### r/i for concrete encased electrode ok 6/27/2002 3:12:48 PM
ELE01-04209 Final6/26/20026/27/20026/27/2002 12:00:00 AMPNR
###-#### not ready 6/27/2002 5:29:35 PM
ELE02-01946 Rough-In Permanent Service6/26/20026/27/20026/27/2002 12:00:00 AMPFAIL
###-#### cor. posted met with contractor250.66 needs #4 GEC 250.52(A)(1) terminate GEC within 5 ft of where u/g enters,250.53(D)(2) needs 2 grd rods ,230.24(A) needs 8 ft over roof 6/27/2002 3:48:16 PM