FIR00-00517
| FIR-Aging Inspection | 6/27/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | | PASS |
|
|
passed by inspector 406 on 10/30/2000 under the building permit history 6/27/2003 11:35:04 AM
|
FIR03-00034
| INSP-Sprinkler Rough-in/Hydro | 6/27/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PASS |
|
|
|
BLD02-02661
| FIRE-Final Inspection | 6/27/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PASS |
|
|
Fire life safety, fire alarm and fire sprinkler finaled
|
FIR03-00326
| INSP-Final Inspection | 6/25/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | FAIL |
|
|
No people or approved plans for the fire sprinkler system were on site. I left a correction notice. I left message on the sprinkler contractors (Tyson) phone 6/27/2003 11:24:43 AM
|
FIR02-00452
| INSP-Sprinkler Rough-in/Hydro | 6/25/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PART |
|
|
sprinkler upright overspaced in switch room 191. Provide documentation that existing sprinkler lines are ok in the west electrical room 6/27/2003 10:56:42 AM
|
FIR03-00049
| INSP-Alarm Testing | 6/26/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PASS |
|
|
MATT; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
FIR03-00207
| INSP-Alarm Testing | 6/26/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PASS |
|
|
MATT; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
FIR03-00193
| INSP-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PASS |
|
|
###-#### Life safety finaled 6/27/2003 10:55:30 AM
|
BLD02-03081
| FIRE-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PASS |
|
|
###-#### Fire life safety, fire alarm and fire sprinkler finaled 6/27/2003 7:51:41 AM
|
FIR03-00313
| INSP-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | FAIL |
|
|
Provide retaining straps for the existing hangers before covering pipe. Pipe is OK to cover after this has been done 6/27/2003 10:57:50 AM
|
FIR03-00294
| INSP-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PASS |
|
|
al; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
FIR01-00330
| INSP-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | A | PASS |
|
|
KEVIN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
FIR03-00128
| INSP-Final Inspection | 6/26/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | P | FAIL |
|
|
Provide additional 175 pendants for the head box, provide the correct orfice in the inspectors test, provide steel pipe and standard pendant in the furnace room, flush underground, lock valves, replace painted pendants, pendant in the kitchen is blocked by a surface mounted light 6/27/2003 1:39:35 PM
|
FIR03-00309
| INSP-Final Inspection | 6/27/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | P | FAIL |
|
|
provide updated map at the facp and nfpa 72 forms 6/27/2003 11:31:02 AM
|
BLD03-00759
| FIRE-Final Inspection | 6/27/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | P | FAIL |
|
|
Can't final life safety until the fire alarm has been finaled but it is ready to be finaled 6/27/2003 11:33:43 AM
|
BLD03-01253
| FIRE-Final Inspection | 6/27/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | P | PART |
|
|
russ; Phone #: ###-#### A temporary occupancy was given until the fire alarm system has been installed and approved. Temp was given with Dave Lokker's permission. All other items are OK 6/27/2003 3:00:13 PM
|
FIR03-00324
| INSP-Sprinkler Rough-in/Hydro | 6/27/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | P | PART |
|
|
russ; Phone #: ###-#### A temporary occupancy was given until the fire alarm system has been installed and approved. Temp was given with Dave Lokker's permission. All other items are OK
|
BLD01-01154
| FIRE-Final Inspection | 6/27/2003 | 6/27/2003 | 6/27/2003 12:00:00 AM | P | PASS |
|
|
Fire life safety and fire sprinklers finaled
|