Inspections for the day of: Friday, June 27, 2003.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR00-00517 FIR-Aging Inspection6/27/20036/27/20036/27/2003 12:00:00 AM PASS
passed by inspector 406 on 10/30/2000 under the building permit history 6/27/2003 11:35:04 AM
FIR03-00034 INSP-Sprinkler Rough-in/Hydro6/27/20036/27/20036/27/2003 12:00:00 AMAPASS
BLD02-02661 FIRE-Final Inspection6/27/20036/27/20036/27/2003 12:00:00 AMAPASS
Fire life safety, fire alarm and fire sprinkler finaled
FIR03-00326 INSP-Final Inspection6/25/20036/27/20036/27/2003 12:00:00 AMAFAIL
No people or approved plans for the fire sprinkler system were on site. I left a correction notice. I left message on the sprinkler contractors (Tyson) phone 6/27/2003 11:24:43 AM
FIR02-00452 INSP-Sprinkler Rough-in/Hydro6/25/20036/27/20036/27/2003 12:00:00 AMAPART
sprinkler upright overspaced in switch room 191. Provide documentation that existing sprinkler lines are ok in the west electrical room 6/27/2003 10:56:42 AM
FIR03-00049 INSP-Alarm Testing6/26/20036/27/20036/27/2003 12:00:00 AMAPASS
MATT; Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR03-00207 INSP-Alarm Testing6/26/20036/27/20036/27/2003 12:00:00 AMAPASS
MATT; Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR03-00193 INSP-Final Inspection6/26/20036/27/20036/27/2003 12:00:00 AMAPASS
###-#### Life safety finaled 6/27/2003 10:55:30 AM
BLD02-03081 FIRE-Final Inspection6/26/20036/27/20036/27/2003 12:00:00 AMAPASS
###-#### Fire life safety, fire alarm and fire sprinkler finaled 6/27/2003 7:51:41 AM
FIR03-00313 INSP-Final Inspection6/26/20036/27/20036/27/2003 12:00:00 AMAFAIL
Provide retaining straps for the existing hangers before covering pipe. Pipe is OK to cover after this has been done 6/27/2003 10:57:50 AM
FIR03-00294 INSP-Final Inspection6/26/20036/27/20036/27/2003 12:00:00 AMAPASS
al; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
FIR01-00330 INSP-Final Inspection6/26/20036/27/20036/27/2003 12:00:00 AMAPASS
KEVIN; Phone #: ###-#### Internet Inspection Request from: Darla Downs
FIR03-00128 INSP-Final Inspection6/26/20036/27/20036/27/2003 12:00:00 AMPFAIL
Provide additional 175 pendants for the head box, provide the correct orfice in the inspectors test, provide steel pipe and standard pendant in the furnace room, flush underground, lock valves, replace painted pendants, pendant in the kitchen is blocked by a surface mounted light 6/27/2003 1:39:35 PM
FIR03-00309 INSP-Final Inspection6/27/20036/27/20036/27/2003 12:00:00 AMPFAIL
provide updated map at the facp and nfpa 72 forms 6/27/2003 11:31:02 AM
BLD03-00759 FIRE-Final Inspection6/27/20036/27/20036/27/2003 12:00:00 AMPFAIL
Can't final life safety until the fire alarm has been finaled but it is ready to be finaled 6/27/2003 11:33:43 AM
BLD03-01253 FIRE-Final Inspection6/27/20036/27/20036/27/2003 12:00:00 AMPPART
russ; Phone #: ###-#### A temporary occupancy was given until the fire alarm system has been installed and approved. Temp was given with Dave Lokker's permission. All other items are OK 6/27/2003 3:00:13 PM
FIR03-00324 INSP-Sprinkler Rough-in/Hydro6/27/20036/27/20036/27/2003 12:00:00 AMPPART
russ; Phone #: ###-#### A temporary occupancy was given until the fire alarm system has been installed and approved. Temp was given with Dave Lokker's permission. All other items are OK
BLD01-01154 FIRE-Final Inspection6/27/20036/27/20036/27/2003 12:00:00 AMPPASS
Fire life safety and fire sprinklers finaled