ELE05-01197
| Final | 6/27/2005 | 6/27/2005 | 6/27/2005 4:13:08 PM | P | PASS |
|
|
dino; Phone #: ###-#### Internet Inspection Request from: Barbara Moore left survey to fix recpts outside. called contr. ok to final
|
ELE05-02123
| Electrical Rough-In | 6/27/2005 | 6/27/2005 | 6/27/2005 3:02:39 PM | P | PASS |
|
|
reinspection for potting on pool light Internet Inspection Request from: Andy Rose potting on pool light ok
|
ELE05-02275
| Temporary Service | 6/26/2005 | 6/27/2005 | 6/27/2005 2:42:34 PM | P | FAIL |
|
|
Internet Inspection Request from: Therrin Robertson called contr, left message, left corr notice, fee due, 250.24(A) gec shall be connected to grounded conductor
|
ELE04-02639
| Permanent Service | 6/24/2005 | 6/27/2005 | 6/27/2005 1:48:40 PM | P | PASS |
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie asked contr to check w/ ipco for available fault current with xfmr being close to switchgear. contr will add 1 more ground clamp to water pipe coming in bldg. p/s u/g n ok
|
ELE05-02258
| Electrical Rough-In | 6/24/2005 | 6/27/2005 | 6/27/2005 12:57:26 PM | P | PASS |
|
|
underground insp.; Phone #: ###-#### Internet Inspection Request from: Heather Packer u/g, pool bond ok
|
ELE05-02270
| Permanent Service | 6/24/2005 | 6/27/2005 | 6/27/2005 9:54:53 AM | A | NH |
|
|
###-#### - terry called number, lady behind said she had key. went toget it, but she didn't know which one. I said to call number on orange card and set up way to make inspection. card on window.
|
ELE05-01745
| Permanent Service | 6/26/2005 | 6/27/2005 | 6/27/2005 9:10:50 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/26/2005 at 3:45:50 PM. Contact: ###-####. corrections made, left correction notice to owner telling him to get permit to bring house up to date. correction notice didn't have a permit number on it. Called owner, left message. This permit should not be final . p/s u/g n ok
|
ELE05-02272
| Temporary Service | 6/24/2005 | 6/27/2005 | 6/27/2005 8:03:09 AM | A | FAIL |
|
|
###-#### - H called contr, left message, left corr notice, 408.4 circuits shall be identified, 408.7 unused openings shall be closed, BCC job id sticker shall be posted, fee due
|