Inspections for the day of: Monday, June 27, 2005.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00045 INSP-Sprinkler Rough-in/Hydro6/24/20056/27/20056/27/2005 3:51:59 PMPFAIL
Attatch retaining strap at hanger first floor nw corner, provide flexible coupling at 4" main where it passes through floor slab, provide retaining nuts on sammy screws at 2nd floor trapeze hangers, provide plans showing upright heads above exterior canopy west side, upright heads at some locations in shell areas 1st and 2nd floors are blocked by truss webs, TI demising walls, and plumbing pipe.
FIR05-00190 INSP-Final Inspection6/27/20056/27/20056/27/2005 2:18:45 PMPCANC
Cancel inspection per Phil Doble, not ready for inspection today.
FIR05-00226 INSP-Final Inspection6/27/20056/27/20056/27/2005 2:17:02 PMPPASS
Door holders have been removed, permit finaled.
FIR05-00069 INSP-Sprinkler Rough-in/Hydro6/24/20056/27/20056/27/2005 1:42:47 PMPPART
Overhead rough-in is good for cover, need all escutcheons on before final.
FIR04-00270 INSP-Supply line flush6/24/20056/27/20056/27/2005 1:30:14 PMPPART
Underground fire supply passed hydrostatic test, still need to witness UG flush.
FIR04-00258 INSP-Sprinkler Rough-in/Hydro6/27/20056/27/20056/27/2005 12:00:00 AMPFAIL
AG hydrostatic test failed, three leaks were found. Rough-in is satisfactory.