Inspections for the day of: Tuesday, June 27, 2006.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02411 Permanent Service6/27/20066/27/20066/27/2006 4:54:45 PMPNR
per bob reichert ok to set up insp for the pm today--jim cell -###-#### talked with owner, ipco didn't come on emergency basis and therefore no equipment set, no grounding done, will call for am inspection
ELE06-02021 Permanent Service6/27/20066/27/20066/27/2006 4:29:07 PMPNR
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, no house panel provisions and no id for tenant panel inside to id which panel
ELE06-02022 Permanent Service6/27/20066/27/20066/27/2006 4:26:41 PMPNR
eric; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, no brkr in meter pak, no panel id inside for house panel
ELE06-01152 Electrical Rough-In6/26/20066/27/20066/27/2006 3:48:06 PMPNR
jerry; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked about 1 1/4", gfci, and make-up, and 12' for max recpt spacing, before inspection
ELE06-02408 Temporary Service6/27/20066/27/20066/27/2006 3:33:01 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g n ok
ELE06-02397 Electrical Rough-In6/27/20066/27/20066/27/2006 3:02:04 PMPPASS
Please inspect trench at this time so customer can backfill it. This is in their unfenced back yard so you have access at all times. Thanks!!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to cover u/g only
ELE06-01492 Permanent Service6/26/20066/27/20066/27/2006 2:22:53 PMPPASS
clyde - call 1/2 hr prior to insp/perm service only; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to cover u/g, p/s o/h n ok
ELE06-02308 Electrical Rough-In6/27/20066/27/20066/27/2006 2:01:33 PMPPASS
Internet Inspection Request from: Tyler Bowen ric ok, p/s u/g n ok
ELE06-02393 Rough-In Permanent Service6/26/20066/27/20066/27/2006 1:29:22 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire called, left corr notice, 300.4(A)(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 312.5 all conductors shall have abrasion protection, 110.12(A) unused openings in box shall be closed, 110.12(C) there shall be no damaged cable, 210.52(A) recpts shall be spaced 12' along floor line
ELE06-02403 Electrical Rough-In6/27/20066/27/20066/27/2006 1:25:44 PMPPASS
Please contact Dan Wilken, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ric ok
ELE06-02400 Electrical Rough-In6/27/20066/27/20066/27/2006 1:25:11 PMPPASS
Please contact Dan Wilken, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ric ok
ELE06-01792 Electrical Rough-In6/26/20066/27/20066/27/2006 11:49:26 AMAPASS
Scheduled by a contractor via Hello! on 6/26/2006 at 1:21:26 PM. Contact: ###-####. ric ok
ELE06-01313 Final6/27/20066/27/20066/27/2006 10:33:21 AMAPART
Scheduled by a contractor via Hello! on 6/27/2006 at 6:19:55 AM. Contact: ###-####. met contr, left corr notice, nec 410.30(C)(1)(1) luminaire shall be directly below recpt, 406.5 faceplate shall completely cover opening 404.9(A) faceplates shall be installed, BCC permanent address and nameplate for meter shall be installed, core and shell of building shall be finalled before tenant space finalled
ELE06-00985 Final6/26/20066/27/20066/27/2006 10:13:10 AMAPASS
Scheduled by a contractor via Hello! on 6/26/2006 at 1:19:37 PM. ok to final
ELE06-02327 Final6/26/20066/27/20066/27/2006 10:12:44 AMAPASS
Scheduled by a contractor via Hello! on 6/26/2006 at 1:16:02 PM. Contact: ###-####. ok to final
ELE06-02350 Final6/26/20066/27/20066/27/2006 9:49:12 AMAPASS
Please call John @ ###-#### or Dallas @ ###-#### at least 30 minutes before arrival. That way they can have someone there to open the building for you. Thanks!!!; Phone #: ###-#### Internet Inspection Request from: Tawnya McKinney ok to final
ELE06-00416 Final6/26/20066/27/20066/27/2006 9:35:56 AMAPART
Phone #: ###-#### Internet Inspection Request from: todd hall called contr, left corr notice, BCC4-05-33(A)(B) equipment shall be listed and labelled by a nationally recognized testing lab,BCC no violations shall be retained,example conduit strapping, gfci outside, kitchen sinks, also need to add plates, bell, verify circuits work on north wall, ceilings ok to cover
ELE06-01834 Electrical Rough-In6/26/20066/27/20066/27/2006 8:49:56 AMAPASS
noble; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
ELE06-02308 Electrical Rough-In6/26/20066/27/20066/27/2006 8:22:10 AMANR
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy no address, saw elect, still working, no job id sticker, said to recall when done
ELE06-01394 Final6/26/20066/27/20066/27/2006 8:21:02 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Eric Shaner corr made, ok to final