Inspections for the day of: Wednesday, June 27, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02303 Electrical Rough-In6/27/20076/27/20076/27/2007 4:19:25 PMPPART
bruce Phone #: ###-#### please call so he can show you were to go 1 new switch in wall ok
ELE07-02295 Electrical Rough-In6/27/20076/27/20076/27/2007 3:53:02 PMPPASS
Lloyd, Rm. #225, please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt walls ok
ELE07-00540 Final6/27/20076/27/20076/27/2007 3:22:07 PMPPASS
JADE Phone #: ###-#### ok
ELE07-02005 Permanent Service6/26/20076/27/20076/27/2007 3:01:06 PMPFAIL
Scheduled by a contractor via Hello! on 6/26/2007 at 7:25:36 PM. Contact: ###-####. corr called all violations not done new one created shall use manufactures listed bonding means not a #10 jumper for 200 amp
ELE07-02279 Electrical Rough-In6/26/20076/27/20076/27/2007 1:17:16 PMAFAIL
mark Phone #: ###-#### corr. fee due
BCC and NEC 110.2 spa not listed, 680.26(B)(5)(1&2) bond gutter down spout, soffit vents , roof metal 680.22(A)(3) needs gfci recept 10ft 20ft partial corr. job not complete
ELE07-01438 Electrical Rough-In6/26/20076/27/20076/27/2007 12:12:26 PMPPART
EQUIPOTENTIAL GRID Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack e grid ok corrections made
ELE07-02294 Electrical Rough-In6/26/20076/27/20076/27/2007 11:03:02 AMAPASS
steve - grounding electrode Phone #: ###-#### electrode ok
ELE07-02230 Temporary Service6/26/20076/27/20076/27/2007 10:30:17 AMAFAIL
dennis Phone #: ###-#### met owner needs conn for GEC seal KOs and needs correct address
ELE07-02043 Permanent Service6/26/20076/27/20076/27/2007 10:10:29 AMAPASS
steve - re-inspection Phone #: ###-####
p/s u/g new ok
ELE07-02157 Rough-In Permanent Service6/27/20076/27/20076/27/2007 9:55:13 AMACANC
Scheduled by a contractor via Hello! on 6/27/2007 at 6:46:19 AM. Contact: ###-####.
ELE07-02158 Rough-In Permanent Service6/27/20076/27/20076/27/2007 9:54:57 AMAPASS
Scheduled by a contractor via Hello! on 6/27/2007 at 6:44:08 AM. Contact: ###-####. p/s u/g new for meter
ELE07-02262 Rough-In Permanent Service6/26/20076/27/20076/27/2007 9:30:33 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn r/i p/s u/g N ok
ELE07-02261 Rough-In Permanent Service6/26/20076/27/20076/27/2007 9:30:04 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn r/i p/s u/g N ok
ELE07-01641 Permanent Service6/26/20076/27/20076/27/2007 8:47:15 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: jesse busack corr. met contr. 110.26(C)(2) shall provide required 2nd exit south wall of elect rm
ELE07-02227 Temporary Service6/26/20076/27/20076/27/2007 8:19:09 AMAPASS
Pat Gill Phone #: ###-#### t/s u/g new ok
ELE07-02293 Final6/26/20076/27/20076/27/2007 12:00:00 AMACANC
Pat Gill Phone #: ###-#### Internet Inspection Request from: Debby Ellis
ELE07-02227 Final6/26/20076/27/20076/27/2007 12:00:00 AMACANC
Pat Gill Phone #: ###-#### Internet Inspection Request from: Debby Ellis