FIR07-00203
| INSP-Sprinkler Rough-in/Hydro | 6/27/2007 | 6/27/2007 | 6/28/2007 2:24:10 PM | P | PART |
|
|
OH hydrostatic test completed satisfactory.
|
FIR07-00529
| INSP-Alarm Testing | 6/26/2007 | 6/27/2007 | 6/28/2007 10:55:06 AM | A | PART |
|
|
FACP and devices passed field testing, however activation of the manual release at the cylinder is not supervised.
|
FIR06-00727
| INSP-Sprinkler Rough-in/Hydro | 6/27/2007 | 6/27/2007 | 6/27/2007 3:49:17 PM | P | FAIL |
|
|
Partial inspection of the dry system for work completed to date as marked on plans, noted overspaced heads at some locations, heads at two areas exceed min.separation, several heads (approx. 35) have been added to cover overbuilds-need to resubmit plans reflecting changes as this work exceeds the scope allowed for field approval.
|
FIR06-00966
| INSP-Final Inspection | 6/27/2007 | 6/27/2007 | 6/27/2007 3:41:12 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD06-01541
| FIRE-Final Inspection | 6/26/2007 | 6/27/2007 | 6/27/2007 2:14:19 PM | A | NR |
|
|
Project not completed for final at this time, pending corrections as discussed.
|
BLD06-01540
| FIRE-Final Inspection | 6/26/2007 | 6/27/2007 | 6/27/2007 2:13:15 PM | A | NR |
|
|
Not completed for final at this time.
|
BLD06-01539
| FIRE-Final Inspection | 6/26/2007 | 6/27/2007 | 6/27/2007 2:12:37 PM | A | NR |
|
|
Pending corrections as discussed.
|
BLD06-01537
| FIRE-Final Inspection | 6/26/2007 | 6/27/2007 | 6/27/2007 2:11:32 PM | A | FAIL |
|
|
Need to remove dust covers and install battey hatches at all smoke detectors, also need to provide an additional SD outside the master bedroom in the immediate vicinity- see fire code review notes for requirements.
|
BLD06-01535
| FIRE-Final Inspection | 6/26/2007 | 6/27/2007 | 6/27/2007 2:10:16 PM | A | FAIL |
|
|
Need to remove dust covers and install battey hatches at all smoke detectors, also need to provide an additional SD outside the master bedroom in the immediate vicinity- see fire code review notes for requirements.
|
BLD06-01538
| FIRE-Final Inspection | 6/26/2007 | 6/27/2007 | 6/27/2007 2:06:54 PM | A | NR |
|
|
Building is not ready for final inspection at this time.
|
FIR07-00077
| INSP-Final Inspection | 6/25/2007 | 6/27/2007 | 6/27/2007 1:02:41 PM | A | PASS |
|
|
Fire alarm work passed final field inspection.
|
FIR07-00313
| INSP-Final Inspection | 6/25/2007 | 6/27/2007 | 6/27/2007 12:21:06 PM | A | FAIL |
|
|
Need map at the panel and signage at the doors to the FACP room as previously requested, vent tube configuration at all duct detectors does not appear to be installed correctly-need mfg. data submittals for verification, re-attatch one ceiling mount strobe on the 2nd floor NE corner, request as-built drawings reflecting field mods. including relocated HP, changed EOL and added horn on the 2nd floor, and deleted monitor points on the first floor, undefined points added to data entry at central station while on site.
|
FIR06-00800
| INSP-Final Inspection | 6/27/2007 | 6/27/2007 | 6/27/2007 10:12:05 AM | P | PASS |
|
|
Building shell and core fire sprinkler permit finaled.
|
FIR07-00316
| INSP-Sprinkler Rough-in | 6/26/2007 | 6/27/2007 | 6/27/2007 9:53:35 AM | A | CANC |
|
|
Per phone call from contractor, UG inspection canceled.
|
BLD06-03574
| FIRE-Final Inspection | 6/26/2007 | 6/27/2007 | 6/27/2007 9:51:33 AM | A | PASS |
|
|
Building final fire life safety inspection passed.
|
FIR07-00311
| INSP-Final Inspection | 6/26/2007 | 6/27/2007 | 6/27/2007 9:50:37 AM | A | PASS |
|
|
Corrections are complete, fire sprinkler permit finaled.
|