Inspections for the day of: Wednesday, June 27, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00958 INSP-Sprinkler Rough-in/Hydro6/26/20076/27/20076/28/2007 10:10:20 AMPPASS
The hydro for the Attic main piping and second floor passed.
There were some brace issues that were remedied by the end of the inspection.
The intermediate area above the kitchen is being sprinkler because the owner didn’t want to insulate as originally agreed upon. The plans for that revision have been submitted to Brian.
FIR07-00493 INSP-Sprinkler Rough-in6/26/20076/27/20076/27/2007 4:38:47 PMAPASS
Sprinkler piping is ok to cover
FIR07-00373 INSP-Final Inspection6/27/20076/27/20076/27/2007 4:36:50 PMPPASS
permit finaled
FIR07-00447 INSP-Final Inspection6/27/20076/27/20076/27/2007 4:32:36 PMPFAIL
No access to building
BLD07-00325 FIRE-Final Inspection6/26/20076/27/20076/27/2007 1:06:25 PMAPASS
Life safety passed. I notified Matt, the contractor that if the access controled egress doors are installed they would have to comply with Chapter 10 of the IFC and IBC.
BLD07-00938 FIRE-Final Inspection6/26/20076/27/20076/27/2007 1:03:57 PMAPASS
Life safety passed. I notified Matt, the contractor that if the access controled egress doors are installed they would have to comply with Chapter 10 of the IFC and IBC.
BLD06-00718 FIRE-Final Inspection6/26/20076/27/20076/27/2007 12:03:46 PMAPASS
Life safety passed.
FIR07-00103 INSP-Sprinkler Rough-in6/26/20076/27/20076/27/2007 11:55:24 AMAPASS
The two pendants in the south side soffit of the second floor elevator lobby are ok to cover
FIR07-00248 INSP-Supply line flush6/26/20076/27/20076/27/2007 10:05:47 AMAFAIL
UG Flush Inspection was not ready. I performed a partial sprinkler rough-in and noted deficiencies such as upright heads blocked by duct work, missing protection under stair landings and upright heads not centered between the trusses.