Inspections for the day of: Friday, June 27, 2008.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00018 INSP-Sprinkler Rough-in6/26/20086/27/20086/30/2008 11:44:20 AMADEFR
Rough-In Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
BLD08-00919 FIRE-Final Inspection6/27/20086/27/20086/27/2008 4:13:10 PMPPART
Need to add exit signage as discussed, will verify and test EM lighting at next scheduled visit, remainder of fire life safety is acceptable.
FIR08-00392 INSP-Final Inspection6/27/20086/27/20086/27/2008 4:11:41 PMPPASS
C/N items verified for compliance, fire sprinkler permit finaled.
BLD08-01003 FIRE-Final Inspection6/26/20086/27/20086/27/2008 3:42:35 PMAPART
Fire life safety is acceptable for the portion of remodeled area west of the demising wall, noted fire extingushers are due annual certification next month (7/08), project final pending completion of permit work at the curently occupied Children's Store.
BLD08-00512 FIRE-Final Inspection6/27/20086/27/20086/27/2008 3:06:58 PMPPART
See city approved plans for area marked in red for tempory occupancy. As per Mark Senteno.Door hardware, exit signs, egress lights and fire extinguishers are approved.One hour rated fire wall shall be completed and approved by Jim Sly before area occupancy. KR
FIR08-00450 INSP-Final Inspection6/26/20086/27/20086/27/2008 2:34:25 PMAPART
Noted one missing a/v and one overspaced notification device at a hallway and conference room on the west side of the 5th floor area. Locations on approved plans are acceptable- field install needs to match per annotations. NOTE: notification at suite 501 passed inspection, suite 500 pending field adjustments.
FIR07-01031 INSP-Sprinkler Rough-in6/27/20086/27/20086/27/2008 2:25:27 PMPPART
See red line areas on plans for areas ok to cover.KR
FIR08-00385 INSP-Sprinkler Rough-in6/26/20086/27/20086/27/2008 2:24:04 PMAFAIL
Pendent heads at the room marked "file storage" are overspaced-need to install per approved plan.
BLD07-03288 FIRE-Final Inspection6/27/20086/27/20086/27/2008 2:08:11 PMPFAIL
Need to remove exit light from rear door, not a public way exit. Shall install exit sign and egress lighting at new door. KR
BLD08-00870 FIRE-Final Inspection6/27/20086/27/20086/27/2008 1:46:25 PMPFAIL
A sprinkler permit was pulled to relocate heads FIR08-00272 and has been passed. A smoke detector was relocate without a permit by Allied General. They will be pulling a quick permit for testing before we can final life safety on building permit. KR
BLD08-01197 FIRE-Final Inspection6/24/20086/27/20086/27/2008 12:58:04 PMPPASS
Fire life safety completed. KR
BLD08-01088 FIRE-Final Inspection6/26/20086/27/20086/27/2008 12:39:32 PMAPASS
Shell only permit. Fire extinguisher will be address on TI permit. KR
BLD08-00080 FIRE-Final Inspection6/26/20086/27/20086/27/2008 12:24:48 PMAPASS
Life safety inspection passed, tactile signage at the area of refuge to be installed when delivered per contractor, public phone line to be installed today-can be verified at next visit for the adjacent project.
FIR08-00158 INSP-Sprinkler Rough-in6/26/20086/27/20086/27/2008 12:23:08 PMAPART
Ok to cover 9' out from building. See city approved plans for details. KR
BLD07-01932 FIRE-Final Inspection6/27/20086/27/20086/27/2008 12:06:30 PMAPART
Building fire life safety approval pending project related fire alarm permit final. EM lights and exit signs tested okay with the exception of one light at the 2nd floor to be repaired today per the electrician, some doors at the 1st floor are not yet installed, need to remove the manual thumbturn at one exit door 1st floor SW side.
FIR08-00047 INSP-Final Inspection6/26/20086/27/20086/27/2008 11:56:54 AMAPART
Final pending completion of elevator controls to enable testing and functionality of recall, shunt trip, fire hat, etc. Remainder of items listed on the correction notice are finished, as-builts accepted. NFPA 72 record of completion forms have not been signed pending elevator testing.
FIR08-00394 INSP-Final Inspection6/26/20086/27/20086/27/2008 11:06:53 AMPCANC
Inspection to be rescheduled.
FIR07-00672 INSP-Final Inspection6/26/20086/27/20086/27/2008 10:52:10 AMAPASS
All fire alarm testing completed. KR
FIR07-00839 INSP-Final Inspection6/26/20086/27/20086/27/2008 10:50:30 AMAFAIL
Exhaust fan shut down during test, fan shall remain on when system is tripped. Electrical power under hood did not shut off.All power under shall shut down. KR
BLD06-03277 FIRE-Final Inspection6/26/20086/27/20086/27/2008 10:37:36 AMAFAIL
All testing completed. Could not pass until kitchen hood system permit is finaled. KR
FIR07-00874 INSP-Sprinkler Rough-in6/26/20086/27/20086/27/2008 10:03:30 AMPCANC
james Note: cover up Phone #: ###-#### Inspection cancelled from web by: Alexandra Rahn
BLD08-00871 BLD-Final6/25/20086/27/20086/26/2008 11:02:44 AMAPASS
Fire life safety finaled.