BLD13-03201
| FIRE-Final Inspection | 6/26/2014 | 6/27/2014 | 6/27/2014 3:51:54 PM | A | FAIL |
|
|
Life safety is ok except the floor plan needs to be resubmitted showing the door on the west end being deleted.
|
FIR14-00222
| INSP-Sprinkler Rough-in | 6/26/2014 | 6/27/2014 | 6/27/2014 2:54:27 PM | P | DONE |
|
|
Inspection was part rough-in and part conference. The dry sprig ups, per conversation with Anthony, are too far from the deck but it appears that Anthony has a solution. I started the rough-in inspection for the piping under the mezzanine but stopped after finding pipe re-routing, elevation changes and alot of additional fittings. Also the "interstitial" space above the first floor ceiling and the second floor is a combustible concealed space with no sprinkler protection. After finding these items I determined that a plan modification will be needed so I stopped inspecting this area. I continued with the upper level piping and found for the most part the rough-in is passed but 25% of the piping has not been instlled yet as well as all of the branchline seimic bracing and earthquake bracing has not been installed yet. There has also been minor pipe routing changes and additional fittings here as well. I also found atleast one flat face bushing being used to reduce a 1 1/2" pipe to 1 1/4".
Per Anthony and I's conversation today, I will be requested to come back out after the plan modifications are approved for a re-inspection.
|
FIR14-00240
| INSP-Sprinkler Rough-in | 6/26/2014 | 6/27/2014 | 6/27/2014 2:23:46 PM | P | PASS |
|
|
Rough-in passed in the Lab area. Piping can be covered.
|
BLD14-01234
| FIRE-Final Inspection | 6/27/2014 | 6/27/2014 | 6/27/2014 1:48:43 PM | P | PASS |
|
|
Life safety passed
|
BLD14-01234
| FIRE-Conference | 6/27/2014 | 6/27/2014 | 6/27/2014 11:39:08 AM | P | DONE |
|
|
Verbally went over sprinkler requirements with Ben
|
FIR14-00237
| INSP-Final Inspection | 6/26/2014 | 6/27/2014 | 6/27/2014 10:53:06 AM | A | PASS |
|
|
Permit finaled
|
FIR14-00352
| INSP-Final Inspection | 6/26/2014 | 6/27/2014 | 6/27/2014 10:52:49 AM | A | PASS |
|
|
Permit finaled
|
FIR14-00230
| INSP-Final Inspection | 6/26/2014 | 6/27/2014 | 6/27/2014 10:52:17 AM | A | PASS |
|
|
Permit finaled
|
FIR14-00222
| INSP-Sprinkler Rough-in | 6/26/2014 | 6/27/2014 | 6/26/2014 9:38:04 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|