ELE17-01612
| Final | 6/26/2017 | 6/27/2017 | 6/27/2017 2:35:10 PM | P | FAIL |
|
|
Final Inspection Please Phone #: ###-#### Inspection requested via web by Kyle Lott IECC-405.2 all interior lighting shalll be controlled by automatic means. As per print shall comply with 2012 international energy compliance code. 110.12- Damaged conduit and box emerging from floor shall be removed or replaced.
|
ELE16-03932
| Electrical Rough-In | 6/27/2017 | 6/27/2017 | 6/27/2017 2:30:08 PM | P | PASS |
|
|
units 323 thru 332 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted sign off in office rough in ok cover
|
ELE17-01964
| Final | 6/27/2017 | 6/27/2017 | 6/27/2017 11:05:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Final ok
|
ELE17-01366
| Final | 6/26/2017 | 6/27/2017 | 6/27/2017 10:18:40 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Ben Final ok
|
ELE17-01337
| Electrical Rough-In | 6/26/2017 | 6/27/2017 | 6/27/2017 9:37:33 AM | A | PASS |
|
|
We are requesting a pool bonding inspection for tomorrow morning. Our contact is Nic @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Pool and hot tub 4- corners, luminaire bonding and underground rough in ok cover
|
ELE17-01994
| Electrical Rough-In | 6/26/2017 | 6/27/2017 | 6/27/2017 9:36:23 AM | A | PASS |
|
|
Please contact Sid McGuire w/questions or comments
THANK YOU AND HAVE A NICE DAY! Phone #: ###-#### Inspection requested via web by JENNY EMEL Discussed energy code requirements, OCC sensors required for alterations. Grid rough in ok cover
|
ELE17-00739
| Electrical Rough-In | 6/26/2017 | 6/27/2017 | 6/27/2017 8:54:52 AM | A | PASS |
|
|
Please contact Sid McGuire w/questions or comments (partial ceiling rough in)
thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL 1st floor soffits rough in ok cover
|
ELE17-01569
| Final | 6/26/2017 | 6/27/2017 | 6/27/2017 8:33:49 AM | A | PASS |
|
|
everything should be good to go Phone #: ###-#### Inspection requested via web by Brad Baker Final ok
|