Inspections for the day of: Tuesday, June 27, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00329 INSP-Conference6/27/20176/27/20176/27/2017 1:59:16 PMPPASS
The underground supply piping is ok for cover
NAF16-00084 INSP-Final6/26/20176/27/20176/27/2017 1:56:52 PMACANC
The fire alarm contractor is not ready for testing yet
FIR17-00144 INSP-Sprinkler Rough-in/Hydro6/26/20176/27/20176/27/2017 10:21:17 AMACANC
Can't do the hydro test until all of the heads have been cut in and piping installed
FIR17-00217 INSP-Sprinkler Rough-in/Hydro6/26/20176/27/20176/27/2017 10:20:38 AMAFAIL
Standpipe hydro failed due to visable leak at the 90/check valve
BLD17-01785 FIRE-Final Inspection6/22/20176/27/20176/27/2017 9:50:06 AMAFAIL
The point of contact did not answer phone, business was unlocked and plans on counter.

Contact plan review/addressing to get the correct address, plans indicate 6909 but tenant space is addressed as 6927. Provide testing of the exit sign/emergency light. Provide one 2A, 10BC fire extinguisher with current inspection tag from a certified company, mount in a normal path of travel no higher than 5' and lower than 4".

mary (ext. 1) Phone #: ###-####
FIR16-00284 INSP-Sprinkler Rough-in6/26/20176/27/20176/27/2017 9:28:01 AMAPASS
Third floor corridor soffits are ok to cover