Inspections for the day of: Wednesday, June 27, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-01328 Final6/27/20186/27/20186/27/2018 3:18:46 PMPFAIL
garage code 2018 Phone #: ###-#### Inspection requested via web by Darryn Coburn
210.70(A)- A single lighting outlet required for habitable rooms shall be connected to a lamp holder or luminaire. Family room has a remote control paddle fan with out a lamp holder or luminaire installed.
356.30-LFNC shall be secured in place at AC unit.
ELE18-02372 Electrical Rough-In6/26/20186/27/20186/27/2018 2:46:13 PMPPASS
Zane-call for access Phone #: ###-####
Cans added thru out, Misc receptacles changed from 1 gang to double duplex, Kitchen and both bathrooms remodelled rough in ok cover
ELE18-02291 Electrical Rough-In6/26/20186/27/20186/27/2018 1:13:40 PMAPART
Contact: Brian Gee Phone #: ###-#### Inspection requested via web by Deb Gooden
Open boxes located above grid, 1 above entry door, 3 above storage area, 1 in center of office. Wall rough in only. Called and left message with contact.
ELE17-02862 Electrical Rough-In6/27/20186/27/20186/27/2018 12:29:51 PMAPASS
Units 412 , 413 ,414 , 415 Phone #: ###-#### Inspection requested via web by Tom Betty Rooms noted rough in ok cover.
ELE18-01727 Electrical Rough-In6/26/20186/27/20186/27/2018 11:10:12 AMAFAIL
Ron Phone #: ###-####

4-05-16- Home owners exemption requires owner to perform work. Friend helping at time of inspection.

110.14- All make up shall be complete, grounds and neutrals.

240.4(D)(3)- Max over current device on 14 gauge wire 15 amps. Some switch legs in bathroom pulled in 14 ga.

300.4- Nail plate where bored hole does not maintain 1 1/4" from framing surface.
300.14- a minimum of 6" of useable wire shall be available at each box.
ELE17-03442 Electrical Rough-In6/26/20186/27/20186/27/2018 11:09:21 AMAPASS
Need to inspect hard lid above NW stairwell for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Area noted rough in ok cover
ELE18-01429 Electrical Rough-In6/26/20186/27/20186/27/2018 9:41:15 AMAPASS
This is for the warm floor in master bathroom. Phone #: ###-#### Inspection requested via web by Bob Glenn Master bath floor heat rough in ok cover
ELE18-01708 Electrical Rough-In6/26/20186/27/20186/27/2018 9:26:15 AMAPASS
This is for the warm floor in master bedroom. Phone #: ###-#### Inspection requested via web by Bob Glenn Master bath floor heat rough in ok cover
ELE18-02394 Rough-In Permanent Service6/26/20186/27/20186/27/2018 9:16:00 AMANR
Phone #: ###-#### Inspection requested via web by Paula Gratiot
Garage not pulled, feeders to garage not done, nail plating not done. Must recall when ready