ELE18-01328
| Final | 6/27/2018 | 6/27/2018 | 6/27/2018 3:18:46 PM | P | FAIL |
|
|
garage code 2018 Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.70(A)- A single lighting outlet required for habitable rooms shall be connected to a lamp holder or luminaire. Family room has a remote control paddle fan with out a lamp holder or luminaire installed. 356.30-LFNC shall be secured in place at AC unit.
|
ELE18-02372
| Electrical Rough-In | 6/26/2018 | 6/27/2018 | 6/27/2018 2:46:13 PM | P | PASS |
|
|
Zane-call for access Phone #: ###-#### Cans added thru out, Misc receptacles changed from 1 gang to double duplex, Kitchen and both bathrooms remodelled rough in ok cover
|
ELE18-02291
| Electrical Rough-In | 6/26/2018 | 6/27/2018 | 6/27/2018 1:13:40 PM | A | PART |
|
|
Contact: Brian Gee Phone #: ###-#### Inspection requested via web by Deb Gooden Open boxes located above grid, 1 above entry door, 3 above storage area, 1 in center of office. Wall rough in only. Called and left message with contact.
|
ELE17-02862
| Electrical Rough-In | 6/27/2018 | 6/27/2018 | 6/27/2018 12:29:51 PM | A | PASS |
|
|
Units 412 , 413 ,414 , 415 Phone #: ###-#### Inspection requested via web by Tom Betty Rooms noted rough in ok cover.
|
ELE18-01727
| Electrical Rough-In | 6/26/2018 | 6/27/2018 | 6/27/2018 11:10:12 AM | A | FAIL |
|
|
Ron Phone #: ###-#### 4-05-16- Home owners exemption requires owner to perform work. Friend helping at time of inspection.
110.14- All make up shall be complete, grounds and neutrals.
240.4(D)(3)- Max over current device on 14 gauge wire 15 amps. Some switch legs in bathroom pulled in 14 ga.
300.4- Nail plate where bored hole does not maintain 1 1/4" from framing surface. 300.14- a minimum of 6" of useable wire shall be available at each box.
|
ELE17-03442
| Electrical Rough-In | 6/26/2018 | 6/27/2018 | 6/27/2018 11:09:21 AM | A | PASS |
|
|
Need to inspect hard lid above NW stairwell for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud Area noted rough in ok cover
|
ELE18-01429
| Electrical Rough-In | 6/26/2018 | 6/27/2018 | 6/27/2018 9:41:15 AM | A | PASS |
|
|
This is for the warm floor in master bathroom. Phone #: ###-#### Inspection requested via web by Bob Glenn Master bath floor heat rough in ok cover
|
ELE18-01708
| Electrical Rough-In | 6/26/2018 | 6/27/2018 | 6/27/2018 9:26:15 AM | A | PASS |
|
|
This is for the warm floor in master bedroom. Phone #: ###-#### Inspection requested via web by Bob Glenn Master bath floor heat rough in ok cover
|
ELE18-02394
| Rough-In Permanent Service | 6/26/2018 | 6/27/2018 | 6/27/2018 9:16:00 AM | A | NR |
|
|
Phone #: ###-#### Inspection requested via web by Paula Gratiot Garage not pulled, feeders to garage not done, nail plating not done. Must recall when ready
|