BLD18-02049
| FIRE-Final Inspection | 6/26/2018 | 6/27/2018 | 6/27/2018 11:18:32 AM | P | FAIL |
|
|
Fire extinguisher needs annual inspection performed. Install property addressing as discussed. Install signage on the interior of the main entry door reading "Door to remain unlocked while building is occupied".
Antonio Phone #: ###-####
|
FIR18-00027
| INSP-Sprinkler Rough-in | 6/27/2018 | 6/27/2018 | 6/27/2018 10:35:20 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete for buidling A levels 1, 2 and 3. General contractor needs to provide documentation for foam sheet insulation rating of installed an the deck, a minimum of R-38 is required for freeze protection on level 3, cover is approved at general contractors risk, if sheeting is not R-38 rated then any cover material over fire sprinkler piping will need to be removed and a R-38 or higher rating will need to be installed. Cover is approved for building A for overhead fire sprinkler piping.
|
FIR18-00027
| INSP-Sprinkler Rough-in/Hydro | 6/26/2018 | 6/27/2018 | 6/27/2018 10:27:30 AM | A | DONE |
|
|
Hydrostatic test witnessed for overhhead fire sprinkler piping for levels 1, 2 and 3 Building A, no pressure loss observed at riser provided gauges.
RANDY CARTRIGHT IS OUR FOREMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|