BLD19-02139
| FIRE-Final Inspection | 6/27/2019 | 6/27/2019 | 6/27/2019 3:50:37 PM | A | CANC |
|
|
Cooridnated for 10AM with point of contact. Please call for access- Linda Phone #: ###-####
|
NAF18-00085
| INSP-Sprinkler Rough-in/Hydro | 6/26/2019 | 6/27/2019 | 6/27/2019 3:41:04 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
NAF18-00083
| INSP-Sprinkler Rough-in/Hydro | 6/26/2019 | 6/27/2019 | 6/27/2019 3:41:03 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
NAF18-00084
| INSP-Sprinkler Rough-in/Hydro | 6/26/2019 | 6/27/2019 | 6/27/2019 3:41:03 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
NAF18-00086
| INSP-Sprinkler Rough-in/Hydro | 6/26/2019 | 6/27/2019 | 6/27/2019 3:41:02 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed.
Contact Andrew Larson ###-#### 30 min prior to OH Hydro Insp start please.
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
NAF18-00086
| INSP-Sprinkler Rough-in | 6/26/2019 | 6/27/2019 | 6/27/2019 3:41:02 PM | P | FAIL |
|
|
Tenting is still not correct on level 4, refer to diagram on city approved drawings for correct install of tenting. Exposed CPVC under stairs on level 1. Head is blocked in garage be garage door bracing, obstruction was mentioned on last inspection. Remote area on level 4 does not match city approved drawings, remote area needs to match or a plan mod needs to be completed showing changes in remote calc area.
Contact Andrew Larson ###-#### 30 min prior to RTC Insp Start please
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR19-00394
| INSP-Sprinkler Rough-in/Hydro | 6/27/2019 | 6/27/2019 | 6/27/2019 1:58:31 PM | P | DONE |
|
|
Hydrostatic test for underground supply witnessed, no pressure loss observed.
underground Phone #: ###-#### Inspection requested via web by Matthew Lewis
|
FIR19-00263
| INSP-Sprinkler Rough-in | 6/26/2019 | 6/27/2019 | 6/27/2019 1:33:52 PM | P | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping above lowered hardlids in kitchen/dining/living room complete, area inspected approved for cover. Exterior battered wall on southwest corner of Area A is filled with non-combustible insulation, area inspected approved for cover. As-builts need to show deleted heads that will no longer be in the area filled with insulation.
Robert Chambers is the contact for this inspection. This rough-in is for the 1st floor area A section 2. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00278
| FIRE-Conference | 6/26/2019 | 6/27/2019 | 6/27/2019 1:31:30 PM | P | DONE |
|
|
Fire conference complete, exterior battered wall on southwest corner of Area A is filled with non-combustible insulation, area inspected approved for cover.
Phone #: ###-#### Inspection requested via web by Corey Hockersmith
|
BLD19-01981
| FIRE-Final Inspection | 6/27/2019 | 6/27/2019 | 6/27/2019 12:39:44 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinuisher will be placed in discussed location and had a current inspection tag. Final life fire safety inspection for area of work complete.
Ariel Phone #: ###-####
|
FIR19-00233
| INSP-Conference | 6/27/2019 | 6/27/2019 | 6/27/2019 12:17:09 PM | P | DONE |
|
|
Gas meter is set in the wrong location, city approved drawings show gas meter by north door, currently meter is set under PIV for fire sprinklers, needs to be relocated to give the required 36 inch clearance around PIV.
|
BLD18-04470
| FIRE-Conference | 6/27/2019 | 6/27/2019 | 6/27/2019 12:10:31 PM | P | CANC |
|
|
|
BLD18-04470
| FIRE-Conference | 6/27/2019 | 6/27/2019 | 6/27/2019 12:10:10 PM | P | DONE |
|
|
Gas meter is set in the wrong location, city approved drawings show gas meter by north door, currently meter is set under PIV for fire sprinklers, needs to be relocated to give the required 36 inch clearance around PIV.
|
FIR19-00327
| INSP-Sprinkler Rough-in | 6/26/2019 | 6/27/2019 | 6/27/2019 10:53:59 AM | A | PASS |
|
|
Tenting has been corrected, all tenting in place at time of inspection. Overhead fire sprinkler piping/tenting approved for cover.
Colton Cox is the contact. This rough-in is for the tinting inspection. Thank you for your hard work! Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-01444
| FIRE-Final Inspection | 6/26/2019 | 6/27/2019 | 6/27/2019 10:37:25 AM | P | PASS |
|
|
Previously noted items have been corrected. Fire sprinkler inspection is complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work comlpete.
Access is through a lock box located in the mailbox beside the door. Code is 2805 Phone #: ###-#### Inspection requested via web by Chad Aland
|
FIR19-00372
| INSP-Sprinkler Rough-in | 6/27/2019 | 6/27/2019 | 6/27/2019 10:18:55 AM | A | FAIL |
|
|
Sprinkler head in foyer is overspaced, head is more than 9 feet off of wall, spacing for this area is 16 X 16 so head needs to be a maximum of 8 feet off of wall. A wall has been added in the office, need to verify if the 20 X 20 spacing will work in this room with the new wall splitting the 2 heads shown on the city approved drawings. As-builts will be required for heads added for beam in entry hallway and changes to floor plan. No tenting installed at time of inspection.
|
FIR19-00372
| INSP-Sprinkler Rough-in/Hydro | 6/27/2019 | 6/27/2019 | 6/27/2019 10:15:17 AM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed at 150PSI instead of the city static pressure, no pressure loss observed.
Call James before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR19-00117
| INSP-Final Inspection | 6/27/2019 | 6/27/2019 | 6/27/2019 9:40:21 AM | P | PASS |
|
|
Previously noted items have been completed, final fire sprinkler inspection complete. Fire sprinkler system is a shared system with the domestic, the lawn sprinklers is pressurized irrigation, not domestic treated water, irrigation shut-down on flow switch not required for this application.
all fixes are done thank you. Phone #: ###-#### Inspection requested via web by jeremiah robison
|
FIR19-00462
| INSP-Final Inspection | 6/26/2019 | 6/27/2019 | 6/27/2019 8:34:53 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
|
FIR19-00462
| INSP-Sprinkler Rough-in | 6/26/2019 | 6/27/2019 | 6/27/2019 8:34:21 AM | A | PASS |
|
|
Rough in inspection for area of work complete.
Contact is Nick Phone #: ###-#### Inspection requested via web by Chris Green
|
BLD19-02139
| FIRE-Final Inspection | 6/26/2019 | 6/27/2019 | 6/27/2019 8:27:34 AM | A | CANC |
|
|
Inspection request is rescheduled for 28JUNE2019 per conversation with point of contact due to scheduling issues on meet up time. Inspection is rescheduled and this request is cancelled.
Please call for access- Linda Phone #: ###-####
|
FIR19-00250
| INSP-Final Inspection | 6/26/2019 | 6/27/2019 | 6/27/2019 8:25:49 AM | P | CANC |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 27, 2019.
|
FIR19-00389
| INSP-Final Inspection | 6/26/2019 | 6/27/2019 | 6/27/2019 7:17:37 AM | A | CANC |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Thursday, June 27, 2019.
|
FIR19-00250
| INSP-Final Inspection | 6/26/2019 | 6/27/2019 | 6/26/2019 11:01:29 AM | A | CANC |
|
|
Phone #: 2088990672 >> Inspection requested via mobile web by Josiah Inspection cancelled via mobile web on Wednesday, June 26, 2019.
|