Inspections for the day of: Friday, June 28, 2002.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00061 INSP-Supply line flush6/27/20026/28/20026/28/2002 12:00:00 AMAFAIL
Inspection was for the stub out only. The thrust blocking and beding is OK but the nuts and bolts need the non corrosive covering. Contractor said it would be taken care of monday 6/28/2002 2:56:37 PM
FIR02-00217 INSP-Supply line flush6/27/20026/28/20026/28/2002 12:00:00 AMAPASS
Underground OK to cover. Hydro or flush not done 6/28/2002 11:42:35 AM
BLD01-02828 FIRE-Final Inspection6/27/20026/28/20026/28/2002 12:00:00 AMAPART
Inspection was not for a final. Inspection was for a tenting inspection. Tenting is OK. Sprinklers OK for cover 6/28/2002 4:04:37 PM
FIR02-00152 INSP-Sprinkler Rough-in/Hydro6/27/20026/28/20026/28/2002 12:00:00 AMAFAIL
hydro test failed. Repair leaks, remove wire from the pipe, alin upright head in attic space with the deck slope, attach hangers and longitudinal EQ braces to the top chord of trusses instead of the bottom chord, retest system and reinspect 6/28/2002 11:22:05 AM
BLD01-03233 FIRE-Final Inspection6/27/20026/28/20026/28/2002 12:00:00 AMAPASS
fire life/safety and fire sprinkler finaled 6/28/2002 10:19:15 AM
FIR02-00011 INSP-Final Inspection6/28/20026/28/20026/28/2002 12:00:00 AMAPASS
fire sprinkler system finaled
FIR02-00186 INSP-Sprinkler Rough-in/Hydro6/28/20026/28/20026/28/2002 12:00:00 AMPPASS
Hydro test ok. Roughin is OK. Need to connect tamper switches to alarm panel, put spare heads in cabinet, provide signs and antifreeze 6/28/2002 3:12:22 PM
MIS02-00131 FIR-Final6/27/20026/28/20026/28/2002 12:00:00 AMPPASS
fire life/safety finaled 6/28/2002 3:33:39 PM
FIR02-00061 INSP-Sprinkler Rough-in/Hydro6/27/20026/28/20026/27/2002 12:00:00 AMACANC
Scheduled by a contractor via Hello! on 06/27/2002 at 13:26:24. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on 06/27/2002 at 13:27:22.