ELE04-01509
| Electrical Rough-In | 6/25/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | A | PASS |
|
|
Larry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok 6/28/2004 9:17:55 AM
|
ELE04-01369
| Final | 6/25/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | A | PASS |
|
|
Contact: Ray Fouts; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok card signed 6/28/2004 10:02:01 AM
|
ELE04-01913
| Conference | 6/25/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | A | DONE |
|
|
Scheduled by a contractor via Hello! on 6/25/2004 at 2:50:59 PM. ok 6/28/2004 10:42:38 AM
|
ELE04-01920
| Permanent Service | 6/25/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | A | PASS |
|
|
perminate service dsl/meter in common area. parcelR5018570180; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
p/s u/g new ok 6/28/2004 8:08:31 AM
|
ELE04-01895
| Rough-In Permanent Service | 6/28/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | A | PASS |
|
|
service is in back lot south east corner; Phone #: ###-#### Internet Inspection Request from: joe wheeler r/i ok for u/g called needs 2 grd rods for p/s
p/s u/g new ok 6/28/2004 8:45:59 AM
|
ELE04-01922
| Permanent Service | 6/28/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | P | NR |
|
|
Contact: Shane Korte; Phone #: ###-#### Internet Inspection Request from: Deb McCoy called needs 2 grd rods, and 10ft from grade to o/h conductors at drip loop 6/28/2004 3:07:08 PM
|
ELE04-01895
| Final | 6/28/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | P | FAIL |
|
|
need ground checked; Phone #: ###-#### Internet Inspection Request from: joe wheeler grd rods only 5ft apart called 6/28/2004 1:19:16 PM
|
ELE04-01926
| Final | 6/28/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | P | FAIL |
|
|
###-#### julie called shall install gfci recepts replaced in kit. correct reversed polarity in basement bed rm recepts note make sure white is neutral and blk is phase at recepts called jf if ? 6/28/2004 2:32:45 PM
|
ELE03-03979
| Final | 6/28/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | P | PASS |
|
|
all electric final ok new contractor is correcting violations made by owner 6/28/2004 2:29:04 PM
|
ELE03-02503
| Permanent Service | 6/28/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | P | PASS |
|
|
p/s o/h rec. ok
|
ELE04-01916
| Permanent Service | 6/25/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | P | PART |
|
|
miller elct - ###-#### no p/s electrode ok for cover 6/28/2004 1:43:29 PM
|
ELE04-01908
| Electrical Rough-In | 6/25/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | P | NR |
|
|
###-#### - barbara needs 2 grd rods, and clean terminals and busing 110.12(C) called 6/28/2004 12:58:09 PM
|
ELE03-02503
| Electrical Rough-In | 6/24/2004 | 6/28/2004 | 6/28/2004 12:00:00 AM | P | PASS |
|
|
###-#### barry ready at 4pm r/i ok
see added p/s 6/28/2004 4:19:55 PM
|