Inspections for the day of: Monday, June 28, 2004.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-01509 Electrical Rough-In6/25/20046/28/20046/28/2004 12:00:00 AMAPASS
Larry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes ok 6/28/2004 9:17:55 AM
ELE04-01369 Final6/25/20046/28/20046/28/2004 12:00:00 AMAPASS
Contact: Ray Fouts; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok card signed 6/28/2004 10:02:01 AM
ELE04-01913 Conference6/25/20046/28/20046/28/2004 12:00:00 AMADONE
Scheduled by a contractor via Hello! on 6/25/2004 at 2:50:59 PM. ok 6/28/2004 10:42:38 AM
ELE04-01920 Permanent Service6/25/20046/28/20046/28/2004 12:00:00 AMAPASS
perminate service dsl/meter in common area. parcelR5018570180; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
p/s u/g new ok 6/28/2004 8:08:31 AM
ELE04-01895 Rough-In Permanent Service6/28/20046/28/20046/28/2004 12:00:00 AMAPASS
service is in back lot south east corner; Phone #: ###-#### Internet Inspection Request from: joe wheeler r/i ok for u/g called needs 2 grd rods for p/s
p/s u/g new ok 6/28/2004 8:45:59 AM
ELE04-01922 Permanent Service6/28/20046/28/20046/28/2004 12:00:00 AMPNR
Contact: Shane Korte; Phone #: ###-#### Internet Inspection Request from: Deb McCoy called needs 2 grd rods, and 10ft from grade to o/h conductors at drip loop 6/28/2004 3:07:08 PM
ELE04-01895 Final6/28/20046/28/20046/28/2004 12:00:00 AMPFAIL
need ground checked; Phone #: ###-#### Internet Inspection Request from: joe wheeler grd rods only 5ft apart called 6/28/2004 1:19:16 PM
ELE04-01926 Final6/28/20046/28/20046/28/2004 12:00:00 AMPFAIL
###-#### julie called shall install gfci recepts replaced in kit. correct reversed polarity in basement bed rm recepts note make sure white is neutral and blk is phase at recepts called jf if ? 6/28/2004 2:32:45 PM
ELE03-03979 Final6/28/20046/28/20046/28/2004 12:00:00 AMPPASS
all electric final ok new contractor is correcting violations made by owner 6/28/2004 2:29:04 PM
ELE03-02503 Permanent Service6/28/20046/28/20046/28/2004 12:00:00 AMPPASS
p/s o/h rec. ok
ELE04-01916 Permanent Service6/25/20046/28/20046/28/2004 12:00:00 AMPPART
miller elct - ###-#### no p/s electrode ok for cover 6/28/2004 1:43:29 PM
ELE04-01908 Electrical Rough-In6/25/20046/28/20046/28/2004 12:00:00 AMPNR
###-#### - barbara needs 2 grd rods, and clean terminals and busing 110.12(C) called 6/28/2004 12:58:09 PM
ELE03-02503 Electrical Rough-In6/24/20046/28/20046/28/2004 12:00:00 AMPPASS
###-#### barry ready at 4pm r/i ok
see added p/s 6/28/2004 4:19:55 PM