Inspections for the day of: Tuesday, June 28, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-00732 Electrical Rough-In6/28/20056/28/20056/28/2005 3:59:26 PMPPASS
richard Note: last of ceiling cover; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE05-02299 Permanent Service6/28/20056/28/20056/28/2005 2:50:33 PMPFAIL
mike0 ###-#### cor. posted called, 110.26 clearence ,250.66 size grds and bonds , 250.24 (A)(1) terminate grds and bonds at neutral bus, 250.52(A)(1) or 104 (A)(1) grd or bond water system, 250.53(B) grd rod shall be 6ft apart
ELE05-02270 Final6/28/20056/28/20056/28/2005 2:03:27 PMPFAIL
Scheduled by a contractor via Hello! on 6/28/2005 at 10:18:38 AM. Contact: ###-####. cor. posted met owner service shall meet current code , no violations to be retained needs clearence for o/h, grounding, main disconnect, proper overcurrent protection for branch circuit, open wiring in walls, protect all exposed cables WH, connectors for all cables
ELE04-01837 Final6/28/20056/28/20056/28/2005 1:17:43 PMPPASS
Internet Inspection Request from: Radon Elaina
ELE05-02277 Rough-In Permanent Service6/28/20056/28/20056/28/2005 1:16:15 PMPPASS
Scheduled by a contractor via Hello! on 6/28/2005 at 7:20:02 AM. Contact: ###-####. r/i ok p/s u/g new ok
ELE05-01684 Electrical Rough-In6/28/20056/28/20056/28/2005 1:15:46 PMPPASS
POOL LIGHT POTTING COMPOUND; Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok
ELE05-02286 Final6/27/20056/28/20056/28/2005 11:40:58 AMAPASS
truss plant - roller line adjacent to the truss line - see James ; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok
ELE05-02283 Electrical Rough-In6/27/20056/28/20056/28/2005 10:18:14 AMAPART
please call for access code///mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa no r/i , conference only need to meet with contractor at job site
ELE05-02122 Final6/27/20056/28/20056/28/2005 9:33:51 AMAPASS
robert; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
ELE05-02281 Permanent Service6/27/20056/28/20056/28/2005 8:49:29 AMAFAIL
kyle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted called 110.26(F)(1) clearence for p/s, 250.24(B) install bond screw, 250.92(A)(3) install bond bushings both ends of nipple between meter and p/s, 240.51&310.16 protect conductors at proper amps and install type S fuses and adaptors evidence of overfusing is present, 250.52(A)(10 or 104(A)(1) grd or bond water system,, B C C no violations to be retained
ELE05-02281 Final6/27/20056/28/20056/28/2005 8:44:04 AMAFAIL
Scheduled by a contractor via Hello! on 6/27/2005 at 3:35:08 PM. Contact: ###-####.
ELE05-02122 Permanent Service6/28/20056/28/20056/28/2005 12:00:00 AMPPASS
robert; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
p/s o/h new ok