FIR02-00051
| INSP-Conference | 6/14/2005 | 6/28/2005 | 6/28/2005 4:24:55 PM | P | NR |
|
|
I left message on Jason's phone for job status
|
FIR05-00284
| INSP-Final Inspection | 6/27/2005 | 6/28/2005 | 6/28/2005 4:24:03 PM | P | CANC |
|
|
JACK; Phone #: ###-#### To be rescheduled for Friday
|
FIR05-00209
| INSP-Final Inspection | 6/27/2005 | 6/28/2005 | 6/28/2005 2:30:53 PM | P | FAIL |
|
|
This inspection was for the sprinkler modifications on the dry system under Concourse B. Need to replace/repair fire proofing affected by hangers and eq bracing, provide hydrostatic test papers and trip test the dry system. Hydro test passed.
|
FIR05-00209
| INSP-Sprinkler Rough-in/Hydro | 6/27/2005 | 6/28/2005 | 6/28/2005 2:30:10 PM | P | PASS |
|
|
This inspection was for the sprinkler modifications on the dry system under Concourse B. Need to replace/repair fire proofing affected by hangers and eq bracing, provide hydrostatic test papers and trip test the dry system. Hydro test passed.
|
FIR05-00156
| FIR-Aging Inspection | 6/28/2005 | 6/28/2005 | 6/28/2005 10:34:54 AM | | NR |
|
|
work is in progress
|
MIS05-00068
| FIR-Final | 6/27/2005 | 6/28/2005 | 6/28/2005 10:32:50 AM | A | PASS |
|
|
Fire life safety finaled
|
BLD04-02203
| FIRE-Final Inspection | 6/28/2005 | 6/28/2005 | 6/28/2005 10:21:00 AM | A | PART |
|
|
Early Completion area is ok to occupy. The pocket door in the pharmacy still needs ada approved hardware prior to a final.
|
FIR05-00190
| INSP-Final Inspection | 6/28/2005 | 6/28/2005 | 6/28/2005 10:20:04 AM | A | PART |
|
|
Early Completion area "C" passed. Heads corrected in GS202 and GS203. Inspected two additional pendant heads which have been circled and dated on city approved plans.
|
FIR05-00274
| INSP-Sprinkler Rough-in/Hydro | 6/27/2005 | 6/28/2005 | 6/28/2005 9:21:46 AM | A | FAIL |
|
|
No approved plans on site. No inspection done.
|
FIR05-00244
| INSP-Sprinkler Rough-in/Hydro | 6/22/2005 | 6/28/2005 | 6/28/2005 9:04:32 AM | A | FAIL |
|
|
Need to certify the fire extinguisher on the first floor and remove all construction debris piles on all floors.
|
FIR05-00277
| INSP-Sprinkler Rough-in | 6/27/2005 | 6/28/2005 | 6/28/2005 8:36:06 AM | A | PASS |
|
|
Rough-in for this tenant space is ok. Ceiling tile is ok to install. Items on the shell correction notice for this area have been corrected.
|