Inspections for the day of: Thursday, June 28, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01884 Final6/28/20076/28/20076/28/2007 3:15:19 PMPPASS
daryl; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr, ok to final
ELE07-01141 Final6/28/20076/28/20076/28/2007 2:23:39 PMPPASS
Scheduled by a contractor via Hello! on 6/28/2007 at 7:51:10 AM. Contact: ###-####. called contr to label inside panels, ok to final, signed occ card
ELE07-00476 Electrical Rough-In6/27/20076/28/20076/28/2007 1:26:28 PMPPART
Scheduled by a contractor via Hello! on 6/27/2007 at 3:20:53 PM. Contact: ###-####. talked to contr, upstairs ceiling only ok to cover, must have new permit to do walls
ELE07-02312 Rough-In Permanent Service6/28/20076/28/20076/28/2007 12:51:30 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called, left corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members (in and outside edges), 334.30 nm cable shall be stapled within 12" of panel, 110.12(C) there shall be no broken parts (outside lite box towards rear), 210.52(A)(2) there shall be recpts installed in 2' wall space and 6' at entry to room (kitchen and family room) BCC address shall be corrected on all permits, yellow card states north, not south
ELE07-02187 Final6/27/20076/28/20076/28/2007 10:53:36 AMAPASS
final on new wiring at cashwrap. Any questions call Tate @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose ok to final
ELE07-01960 Final6/26/20076/28/20076/28/2007 10:22:44 AMAPASS
MAX. FAULT CURRENT IS 9812.09 SYMMETRICAL AMPS PER DAVE BOOTS @ IPCO. PHONE # ###-#### Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to final
ELE07-00054 Final6/28/20076/28/20076/28/2007 10:02:02 AMAFAIL
met bldr, called contr, left corr notice, nec 210.70(C) light shall be installed 2nd story a/c room, BCC main floor sw room shall have switch installed and recpts shall be correct polarity, no open gnds, 210.8(A)(3) rear outside recpt shall be gfci protected
ELE07-00266 Final6/27/20076/28/20076/28/2007 9:54:04 AMACANC
bill - barn only Phone #: ###-#### wrong permit number, should be 7-54,see comments on correct permit
ELE07-01589 Final6/27/20076/28/20076/28/2007 9:23:48 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Latisha Peltier ok to final
ELE07-00573 Electrical Rough-In6/27/20076/28/20076/28/2007 9:03:46 AMPCANC
Scheduled by a contractor via Hello! on 6/27/2007 at 8:25:19 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jun 28 2007 9:03AM.
ELE07-02280 Permanent Service6/27/20076/28/20076/28/2007 8:32:55 AMAPASS
Phone #: ###-#### p/s o/h rec ok
ELE07-02311 Electrical Rough-In6/28/20076/28/20076/28/2007 8:11:49 AMAPASS
Scheduled by a contractor via Hello! on 6/28/2007 at 6:52:07 AM. Contact: ###-####. ok to cover walls only