ELE07-01884
| Final | 6/28/2007 | 6/28/2007 | 6/28/2007 3:15:19 PM | P | PASS |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr, ok to final
|
ELE07-01141
| Final | 6/28/2007 | 6/28/2007 | 6/28/2007 2:23:39 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 6/28/2007 at 7:51:10 AM. Contact: ###-####. called contr to label inside panels, ok to final, signed occ card
|
ELE07-00476
| Electrical Rough-In | 6/27/2007 | 6/28/2007 | 6/28/2007 1:26:28 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 6/27/2007 at 3:20:53 PM. Contact: ###-####. talked to contr, upstairs ceiling only ok to cover, must have new permit to do walls
|
ELE07-02312
| Rough-In Permanent Service | 6/28/2007 | 6/28/2007 | 6/28/2007 12:51:30 PM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Cevyn Recla called, left corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members (in and outside edges), 334.30 nm cable shall be stapled within 12" of panel, 110.12(C) there shall be no broken parts (outside lite box towards rear), 210.52(A)(2) there shall be recpts installed in 2' wall space and 6' at entry to room (kitchen and family room) BCC address shall be corrected on all permits, yellow card states north, not south
|
ELE07-02187
| Final | 6/27/2007 | 6/28/2007 | 6/28/2007 10:53:36 AM | A | PASS |
|
|
final on new wiring at cashwrap. Any questions call Tate @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose ok to final
|
ELE07-01960
| Final | 6/26/2007 | 6/28/2007 | 6/28/2007 10:22:44 AM | A | PASS |
|
|
MAX. FAULT CURRENT IS 9812.09 SYMMETRICAL AMPS PER DAVE BOOTS @ IPCO. PHONE # ###-#### Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to final
|
ELE07-00054
| Final | 6/28/2007 | 6/28/2007 | 6/28/2007 10:02:02 AM | A | FAIL |
|
|
met bldr, called contr, left corr notice, nec 210.70(C) light shall be installed 2nd story a/c room, BCC main floor sw room shall have switch installed and recpts shall be correct polarity, no open gnds, 210.8(A)(3) rear outside recpt shall be gfci protected
|
ELE07-00266
| Final | 6/27/2007 | 6/28/2007 | 6/28/2007 9:54:04 AM | A | CANC |
|
|
bill - barn only Phone #: ###-#### wrong permit number, should be 7-54,see comments on correct permit
|
ELE07-01589
| Final | 6/27/2007 | 6/28/2007 | 6/28/2007 9:23:48 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Latisha Peltier ok to final
|
ELE07-00573
| Electrical Rough-In | 6/27/2007 | 6/28/2007 | 6/28/2007 9:03:46 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 6/27/2007 at 8:25:19 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jun 28 2007 9:03AM.
|
ELE07-02280
| Permanent Service | 6/27/2007 | 6/28/2007 | 6/28/2007 8:32:55 AM | A | PASS |
|
|
Phone #: ###-#### p/s o/h rec ok
|
ELE07-02311
| Electrical Rough-In | 6/28/2007 | 6/28/2007 | 6/28/2007 8:11:49 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/28/2007 at 6:52:07 AM. Contact: ###-####. ok to cover walls only
|