Inspections for the day of: Thursday, June 28, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Strole
TitlePLM/MEC-INSPECTOR
Phone #794-7913
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM07-01418 Groundwork6/27/20076/28/20076/29/2007 3:07:43 PMAPART
GREASE TANK INSPECTION; JOB CONTACT THAYNE Phone #: ###-#### Internet Inspection Request from: ADAM WARR-inlet & outlet piping on grease trap pass-grease trap still needs to be tested.grease trap pass
PLM07-01284 Final6/27/20076/28/20076/28/2007 5:12:21 PMAPART
CONTACT IS MIKE WEBB ###-#### Phone #: ###-#### Internet Inspection Request from: MARGGIE BUSS-no final till permit for dbcv for lawn sprinklers in issued.
PLM05-04309 Plumbing Rough-in6/28/20076/28/20076/28/2007 4:50:26 PMPCANC
Scheduled by a contractor via Hello! on 6/28/2007 at 11:04:28 AM. Contact: ###-####.
PLM07-01248 Final6/28/20076/28/20076/28/2007 4:49:02 PMPFAIL
lon; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang-need avb's on all beauty sinks or use proper fcts,w/h flex can be no longer then 24"-dbcv for building needs tested & certified.
PLM07-01874 Plumbing Rough-in6/27/20076/28/20076/28/2007 4:12:10 PMPPART
JOHN Phone #: ###-####-need to test g/w
PLM07-02191 Plumbing Rough-in6/28/20076/28/20076/28/2007 3:56:09 PMPPASS
Scheduled by a contractor via Hello! on 6/28/2007 at 6:41:53 AM. Contact: ###-####.
PLM07-00334 Final6/27/20076/28/20076/28/2007 3:33:49 PMAFAIL
josh Phone #: ###-####-need air gap on t&p-dbcv needs tested & certified-public lavs need 120 degree water or less.
PLM07-01601 Final6/27/20076/28/20076/28/2007 3:03:54 PMAPASS
Scheduled by a contractor via Hello! on 6/27/2007 at 10:37:06 PM. Contact: ###-####.
PLM07-02215 Final6/27/20076/28/20076/28/2007 2:48:48 PMAPASS
Please call Jay with questions @ ###-#### Phone #: ###-#### Internet Inspection Request from: Roger Patterson
PLM07-02204 Groundwork6/27/20076/28/20076/28/2007 2:32:41 PMPPASS
Scheduled by a contractor via Hello! on 6/27/2007 at 8:17:37 PM. Contact: ###-####.
PLM07-00883 Plumbing Rough-in6/27/20076/28/20076/28/2007 2:17:41 PMADONE
Adi ###-####-this was a conferance.
PLM07-00840 Final6/27/20076/28/20076/28/2007 12:53:12 PMAPART
CONTACT: MIKE W Phone #: ###-#### Internet Inspection Request from: JENN STALEY-need permit for 2 rpba's,need to label non potable water & run drains to approved location.
PLM07-02152 Plumbing Rough-in6/28/20076/28/20076/28/2007 12:00:00 AMPCANC
mike - re-inspection Phone #: ###-####