Inspections for the day of: Tuesday, June 28, 2011.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-00600 ELE-Aging Inspection6/28/20116/28/20117/1/2011 3:25:17 PM DONE
see final
ELE10-00599 ELE-Aging Inspection6/28/20116/28/20117/1/2011 3:24:34 PM DONE
see final
GCE11-00073 GCE-Temporary Service6/28/20116/28/20116/28/2011 3:47:50 PMPPASS
contractor at ###-#### t/s u/g ok
ELE11-01214 Electrical Rough-In6/28/20116/28/20116/28/2011 3:19:58 PMPPASS
tim please call for area that was requested for inspection. Phone #: ###-#### rough-in ok cover ceiling grid
ELE11-01385 Final6/28/20116/28/20116/28/2011 2:46:44 PMPFAIL
ray Phone #: ###-#### Need to install weather resistanted service outlet within 25 feet of a/c unit
ELE11-01388 Conference6/28/20116/28/20116/28/2011 2:25:47 PMPDONE
Kenny Phone #: ###-#### Discussed service panel locations, GFCI protection on two wire circuits
ELE11-01373 Permanent Service6/28/20116/28/20116/28/2011 1:40:58 PMPFAIL
rick Phone #: ###-#### Reconnect service mask guide wires. NEC 250.56 Install 2- 8 foot ground rods six feet apart. NEC 250.64 shall install metallic connector listed for grounding & bonding where grounding electrode conductor enters service or use non-metallic connector. Check water piping to house, if metal, needs bonding to service
ELE11-00918 Final6/28/20116/28/20116/28/2011 1:06:26 PMPPASS
Please call when on your way, to guarantee entrance. Phone #: ###-#### >> Inspection requested via web by mike brown final ok
ELE11-01001 Permanent Service6/28/20116/28/20116/28/2011 12:55:15 PMPPASS
Todd Phone #: ###-#### p/s u/g n ok
ELE11-01386 Temporary Service6/28/20116/28/20116/28/2011 12:33:24 PMPFAIL
Kevin ###-#### Temp poles require job identification tag NEC 406.8(B) All 15 and 20 ampere receptacle in wet locations require listed weather resistanted type.
ELE11-01373 Conference6/27/20116/28/20116/28/2011 10:14:06 AMADONE
Rick please call 30 min before going out Phone #: ###-#### power has been off for over 12 months.
ELE11-01376 Conference6/27/20116/28/20116/28/2011 10:07:33 AMADONE
SUZI PLEASE CALL 30 MIN BEFORE GOING OUT Phone #: ###-#### Home owner adding single outlet for wall mount tv set, Discussed freewire, wire terminations, wire size.
ELE11-01145 Final6/27/20116/28/20116/28/2011 9:41:33 AMAFAIL
Richard Phone #: ###-#### NEC 210.52 (c)(1) A receptacle outlet shall be installed at each wall countertop that is 12 inchs or wider. NEC210.8 kitchen--Where receptacles installed within 6 feet of outside edge of the sink, require GFCI protection
ELE10-01747 Final6/27/20116/28/20116/28/2011 9:33:15 AMAPASS
Richard Phone #: ###-#### final ok
ESC10-00830 Aging Inspection6/28/20116/28/20116/28/2011 9:12:03 AM DONE
see final
ESC10-00830 Site Final6/28/20116/28/20116/28/2011 9:11:21 AMPPASS
final ok site clean, landscaping in
ELE11-01280 Final6/28/20116/28/20116/28/2011 9:06:05 AMPPASS
final ok
ELE11-01280 Electrical Rough-In6/27/20116/28/20116/28/2011 9:05:34 AMAPASS
ready to final >> Inspection requested via web by joel smith rough-in ok should be final
ELE11-01035 Final6/28/20116/28/20116/28/2011 8:44:26 AMAPASS
Cal, Key under outdoor stairs on hook, Phone #: ###-#### >> Inspection requested via web by cal crosby final ok