ELE10-00600
| ELE-Aging Inspection | 6/28/2011 | 6/28/2011 | 7/1/2011 3:25:17 PM | | DONE |
|
|
see final
|
ELE10-00599
| ELE-Aging Inspection | 6/28/2011 | 6/28/2011 | 7/1/2011 3:24:34 PM | | DONE |
|
|
see final
|
GCE11-00073
| GCE-Temporary Service | 6/28/2011 | 6/28/2011 | 6/28/2011 3:47:50 PM | P | PASS |
|
|
contractor at ###-#### t/s u/g ok
|
ELE11-01214
| Electrical Rough-In | 6/28/2011 | 6/28/2011 | 6/28/2011 3:19:58 PM | P | PASS |
|
|
tim please call for area that was requested for inspection. Phone #: ###-#### rough-in ok cover ceiling grid
|
ELE11-01385
| Final | 6/28/2011 | 6/28/2011 | 6/28/2011 2:46:44 PM | P | FAIL |
|
|
ray Phone #: ###-#### Need to install weather resistanted service outlet within 25 feet of a/c unit
|
ELE11-01388
| Conference | 6/28/2011 | 6/28/2011 | 6/28/2011 2:25:47 PM | P | DONE |
|
|
Kenny Phone #: ###-#### Discussed service panel locations, GFCI protection on two wire circuits
|
ELE11-01373
| Permanent Service | 6/28/2011 | 6/28/2011 | 6/28/2011 1:40:58 PM | P | FAIL |
|
|
rick Phone #: ###-#### Reconnect service mask guide wires. NEC 250.56 Install 2- 8 foot ground rods six feet apart. NEC 250.64 shall install metallic connector listed for grounding & bonding where grounding electrode conductor enters service or use non-metallic connector. Check water piping to house, if metal, needs bonding to service
|
ELE11-00918
| Final | 6/28/2011 | 6/28/2011 | 6/28/2011 1:06:26 PM | P | PASS |
|
|
Please call when on your way, to guarantee entrance. Phone #: ###-#### >> Inspection requested via web by mike brown final ok
|
ELE11-01001
| Permanent Service | 6/28/2011 | 6/28/2011 | 6/28/2011 12:55:15 PM | P | PASS |
|
|
Todd Phone #: ###-#### p/s u/g n ok
|
ELE11-01386
| Temporary Service | 6/28/2011 | 6/28/2011 | 6/28/2011 12:33:24 PM | P | FAIL |
|
|
Kevin ###-#### Temp poles require job identification tag NEC 406.8(B) All 15 and 20 ampere receptacle in wet locations require listed weather resistanted type.
|
ELE11-01373
| Conference | 6/27/2011 | 6/28/2011 | 6/28/2011 10:14:06 AM | A | DONE |
|
|
Rick please call 30 min before going out Phone #: ###-#### power has been off for over 12 months.
|
ELE11-01376
| Conference | 6/27/2011 | 6/28/2011 | 6/28/2011 10:07:33 AM | A | DONE |
|
|
SUZI PLEASE CALL 30 MIN BEFORE GOING OUT Phone #: ###-#### Home owner adding single outlet for wall mount tv set, Discussed freewire, wire terminations, wire size.
|
ELE11-01145
| Final | 6/27/2011 | 6/28/2011 | 6/28/2011 9:41:33 AM | A | FAIL |
|
|
Richard Phone #: ###-#### NEC 210.52 (c)(1) A receptacle outlet shall be installed at each wall countertop that is 12 inchs or wider. NEC210.8 kitchen--Where receptacles installed within 6 feet of outside edge of the sink, require GFCI protection
|
ELE10-01747
| Final | 6/27/2011 | 6/28/2011 | 6/28/2011 9:33:15 AM | A | PASS |
|
|
Richard Phone #: ###-#### final ok
|
ESC10-00830
| Aging Inspection | 6/28/2011 | 6/28/2011 | 6/28/2011 9:12:03 AM | | DONE |
|
|
see final
|
ESC10-00830
| Site Final | 6/28/2011 | 6/28/2011 | 6/28/2011 9:11:21 AM | P | PASS |
|
|
final ok site clean, landscaping in
|
ELE11-01280
| Final | 6/28/2011 | 6/28/2011 | 6/28/2011 9:06:05 AM | P | PASS |
|
|
final ok
|
ELE11-01280
| Electrical Rough-In | 6/27/2011 | 6/28/2011 | 6/28/2011 9:05:34 AM | A | PASS |
|
|
ready to final >> Inspection requested via web by joel smith rough-in ok should be final
|
ELE11-01035
| Final | 6/28/2011 | 6/28/2011 | 6/28/2011 8:44:26 AM | A | PASS |
|
|
Cal, Key under outdoor stairs on hook, Phone #: ###-#### >> Inspection requested via web by cal crosby final ok
|