ELE13-01376
| Temporary Service | 6/28/2013 | 6/28/2013 | 6/28/2013 3:11:27 PM | P | PASS |
|
|
Contact: Frank Yantis Phone #: ###-#### >> Inspection requested via web by Deb Gooden t/s o/h n ok
|
ELE13-01599
| Conference | 6/28/2013 | 6/28/2013 | 6/28/2013 3:00:55 PM | P | DONE |
|
|
Boise Municipal Code 4-05-32- Code Violation Not To Be Retained. NEC 110.26(F)- Dedicated equiptment space, area directly above and below is dedicated equiptment space. Gas meter is located directly below existing location. NEC 394.12- Concealed Knob and Tube Wiring, uses not permitted. (5)- Hollow spaces of walls, ceilings and attics where such spaces are insulated by loose, rolled, or foamed in place insulating material that envelopes conductors. This is a fire hazard.
|
MIS13-00185
| ELE-Conference | 6/27/2013 | 6/28/2013 | 6/28/2013 2:11:24 PM | A | FAIL |
|
|
call Alex when go out ###-####//electrical inspection for occupancy For occupancy tenant shall hire electrical contractor to- -Remove all NM cable in and on building. -Remove or repair all conduits, cables, and boxes. -Cover all open junction boxes. -Provide proper covers for devices mounted to boxes. -Verify of provide service equiptment grounding. -Label all disconnects and service switches. All items listed are required by Boise Municipal Code and National Electric Code.
|
ELE13-01673
| Final | 6/28/2013 | 6/28/2013 | 6/28/2013 12:56:00 PM | P | CANC |
|
|
If any questions can call Brad at Alloway Elect Phone #: ###-#### >> Inspection requested via web by brad williams Needed rough in inspection
|
ELE13-01673
| Electrical Rough-In | 6/28/2013 | 6/28/2013 | 6/28/2013 12:54:57 PM | P | PASS |
|
|
If any questions can call Brad at Alloway Elect Phone #: ###-#### >> Inspection requested via web by brad williams Bathroom remodel rough in ok cover
|
ELE13-00514
| Final | 6/28/2013 | 6/28/2013 | 6/28/2013 11:48:15 AM | P | PASS |
|
|
AC unit branch circuit and ground fault protection compiant with code. Final ok
|
ELE13-01251
| Final | 6/27/2013 | 6/28/2013 | 6/28/2013 10:25:01 AM | A | PASS |
|
|
###-#### Phone #: ###-#### >> Inspection requested via web by Mark M No card posted Final ok
|
ELE13-01633
| Final | 6/27/2013 | 6/28/2013 | 6/28/2013 9:50:34 AM | A | PASS |
|
|
Contact: Marty Vanness Phone #: ###-#### >> Inspection requested via web by Deb Gooden Corrections made final ok
|
ELE13-01633
| Electrical Rough-In | 6/28/2013 | 6/28/2013 | 6/28/2013 9:50:24 AM | P | PASS |
|
|
Contact: Marty Vanness Phone #: ###-#### >> Inspection requested via web by Deb Gooden moving of panel to create sufitient work space rough in ok
|
ELE13-01671
| Rough-In Permanent Service | 6/28/2013 | 6/28/2013 | 6/28/2013 9:33:49 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI 300.4- NM cable shall be secured at least 1 1/4" from surface of framing member. 334.30 NM cable shall be secured with in 12" of bath fan j-box. 314.4- Metal boxes shall be grounded and bonded. 250.112- non current carrying metal parts shall be grounded.
|
ELE13-01663
| Rough-In Permanent Service | 6/27/2013 | 6/28/2013 | 6/28/2013 8:55:12 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Michael Paradis Inlaws addition rough in ok cover
|