Inspections for the day of: Friday, June 28, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01376 Temporary Service6/28/20136/28/20136/28/2013 3:11:27 PMPPASS
Contact: Frank Yantis Phone #: ###-#### >> Inspection requested via web by Deb Gooden t/s o/h n ok
ELE13-01599 Conference6/28/20136/28/20136/28/2013 3:00:55 PMPDONE
Boise Municipal Code 4-05-32- Code Violation Not To Be Retained.
NEC 110.26(F)- Dedicated equiptment space, area directly above and below is dedicated equiptment space. Gas meter is located directly below existing location.
NEC 394.12- Concealed Knob and Tube Wiring, uses not permitted. (5)- Hollow spaces of walls, ceilings and attics where such spaces are insulated by loose, rolled, or foamed in place insulating material that envelopes conductors. This is a fire hazard.
MIS13-00185 ELE-Conference6/27/20136/28/20136/28/2013 2:11:24 PMAFAIL
call Alex when go out ###-####//electrical inspection for occupancy
For occupancy tenant shall hire electrical contractor to-
-Remove all NM cable in and on building.
-Remove or repair all conduits, cables, and boxes.
-Cover all open junction boxes.
-Provide proper covers for devices mounted to boxes.
-Verify of provide service equiptment grounding.
-Label all disconnects and service switches.
All items listed are required by Boise Municipal Code and National Electric Code.
ELE13-01673 Final6/28/20136/28/20136/28/2013 12:56:00 PMPCANC
If any questions can call Brad at Alloway Elect Phone #: ###-#### >> Inspection requested via web by brad williams Needed rough in inspection
ELE13-01673 Electrical Rough-In6/28/20136/28/20136/28/2013 12:54:57 PMPPASS
If any questions can call Brad at Alloway Elect Phone #: ###-#### >> Inspection requested via web by brad williams Bathroom remodel rough in ok cover
ELE13-00514 Final6/28/20136/28/20136/28/2013 11:48:15 AMPPASS
AC unit branch circuit and ground fault protection compiant with code. Final ok
ELE13-01251 Final6/27/20136/28/20136/28/2013 10:25:01 AMAPASS
###-#### Phone #: ###-#### >> Inspection requested via web by Mark M
No card posted Final ok
ELE13-01633 Final6/27/20136/28/20136/28/2013 9:50:34 AMAPASS
Contact: Marty Vanness Phone #: ###-#### >> Inspection requested via web by Deb Gooden Corrections made final ok
ELE13-01633 Electrical Rough-In6/28/20136/28/20136/28/2013 9:50:24 AMPPASS
Contact: Marty Vanness Phone #: ###-#### >> Inspection requested via web by Deb Gooden moving of panel to create sufitient work space rough in ok
ELE13-01671 Rough-In Permanent Service6/28/20136/28/20136/28/2013 9:33:49 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI
300.4- NM cable shall be secured at least 1 1/4" from surface of framing member.
334.30 NM cable shall be secured with in 12" of bath fan j-box.
314.4- Metal boxes shall be grounded and bonded.
250.112- non current carrying metal parts shall be grounded.
ELE13-01663 Rough-In Permanent Service6/27/20136/28/20136/28/2013 8:55:12 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Michael Paradis
Inlaws addition rough in ok cover