FIR13-00270
| INSP-Sprinkler Rough-in | 6/28/2013 | 6/28/2013 | 7/1/2013 5:44:26 PM | P | PART |
|
|
New DP heads in the deli service cooler okayed.
|
FIR13-00148
| INSP-Final Inspection | 6/28/2013 | 6/28/2013 | 6/28/2013 4:27:48 PM | P | PART |
|
|
Verified added coverage at the tops of both the north and south stairways per plan modification.
|
FIR12-00605
| FIR-Aging Inspection | 6/28/2013 | 6/28/2013 | 6/28/2013 3:24:03 PM | | DONE |
|
|
Site work in progress
|
FIR12-00634
| FIR-Aging Inspection | 6/28/2013 | 6/28/2013 | 6/28/2013 3:23:35 PM | | DONE |
|
|
Site work in progress
|
BLD13-01405
| FIRE-Final Inspection | 6/28/2013 | 6/28/2013 | 6/28/2013 3:22:40 PM | P | PASS |
|
|
Life safety passed.
|
FIR13-00242
| INSP-Final Inspection | 6/27/2013 | 6/28/2013 | 6/28/2013 3:22:03 PM | A | PASS |
|
|
C/N items completed and verified. Hood suppression permit finaled.
|
FIR13-00057
| INSP-Sprinkler Rough-in | 6/28/2013 | 6/28/2013 | 6/28/2013 3:20:59 PM | A | PART |
|
|
Overhead work at grid ceilings in rooms 303, 304, and 305 including the meeting room are okay to cover.
|
FIR13-00116
| INSP-Sprinkler Rough-in/Hydro | 6/27/2013 | 6/28/2013 | 6/28/2013 3:19:19 PM | A | PART |
|
|
Overhead hydrostatic test of the new dry and wet systems passed. Also okayed for cover work at sheetrock ceilings in the bike room, and west entryway.
|
FIR13-00231
| INSP-Final Inspection | 6/28/2013 | 6/28/2013 | 6/28/2013 11:49:15 AM | P | PASS |
|
|
Fire sprinkler permit passed final walkthrough.
|
FIR12-00586
| INSP-Sprinkler Rough-in/Hydro | 6/27/2013 | 6/28/2013 | 6/28/2013 11:48:04 AM | A | PART |
|
|
Remainder of UG fire supply line okayed for cover- added 90's to be included on plan modification as well as retainer glands in place of thrust blocking.
|
BLD13-00805
| FIRE-Final Inspection | 6/27/2013 | 6/28/2013 | 6/28/2013 11:45:56 AM | A | NR |
|
|
Missing exit sign face plate, doors and hardware are not yet installed, missing one fire sprinkler escutcheon at the SW corner office, could not locate approved plans on site.
|
BLD13-01272
| FIRE-Final Inspection | 6/27/2013 | 6/28/2013 | 6/28/2013 11:44:09 AM | A | PASS |
|
|
Fire life safety inspection completed satisfactory.
|
BLD13-01405
| FIRE-Final Inspection | 6/27/2013 | 6/28/2013 | 6/28/2013 11:43:19 AM | A | PASS |
|
|
Correction items verified for completion. Life safety finaled.
|