Inspections for the day of: Wednesday, June 28, 2017.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTom Saunders
TitleELE-INSPECTOR
Phone #208-794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03529 Electrical Rough-In6/28/20176/28/20176/28/2017 2:04:08 PMPPASS
Dining, activity, barista, salon Phone #: ###-#### Inspection requested via web by Bryan Atkins..

junction boxes over offices complete, areas as marked dated on plans...ok to cover
ELE17-01570 Final6/28/20176/28/20176/28/2017 12:50:23 PMPNR
Phone #: ###-#### Inspection requested via web by Christian Kilpatrick...

not ready for final...will need to schedule for next day
ELE17-01570 Electrical Rough-In6/27/20176/28/20176/28/2017 12:49:32 PMPPASS
Electrician: George Stanton Phone #: ###-#### Inspection requested via web by Christian Kilpatrick...

standard equipment...UL listings provided..plans on sight...ok
ELE17-02053 Temporary Service6/28/20176/28/20176/28/2017 12:29:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn...

t/s u/g n ok
ELE17-01937 Permanent Service6/28/20176/28/20176/28/2017 12:09:58 PMAPASS
Late AM for inspection. Service upgrade for spa. Phone #: ###-#### Inspection requested via web by Rowdy Monroe...

p/s u/g rec ok
ELE17-01937 Electrical Rough-In6/28/20176/28/20176/28/2017 12:09:34 PMPPASS
Late AM for inspection. Service upgrade for spa. Phone #: ###-#### Inspection requested via web by Rowdy Monroe...

circuit for freezers and circuit for hot tub....hot tub hook up will be done on seperate permit
ELE17-01109 Final6/28/20176/28/20176/28/2017 10:35:20 AMPPASS
Key is under small rock to right of front stair Phone #: ###-#### Inspection requested via web by Jason Wicks...

permit was only for remodelling kitchen, laundry, and 2 bathrooms...added grounding on service only...ok to final
ELE13-02103 Final6/28/20176/28/20176/28/2017 10:04:19 AMPPASS
ok to final
ELE17-01842 Final6/27/20176/28/20176/28/2017 10:00:24 AMAPASS
Call Steve at ###-#### with any questions. Thank You Phone #: ###-#### Inspection requested via web by Steve Blackmer...

correction made...ok to final
ELE17-01969 Conference6/26/20176/28/20176/28/2017 9:36:00 AMAPASS
Kelly Phone #: ###-####...

discussed new bath requirements, gave him frequently asked questions paperwork, knowledgeable in work being performed
ELE17-00182 Final6/27/20176/28/20176/28/2017 9:10:44 AMAFAIL
code 8199 Phone #: ###-#### Inspection requested via web by Neal Rumsey...

1. missing plate on switches at fireplace
2. all bath outlets shall have GFI protection...outlets within 6ft of sink shall have GFI protection...outlet down low in mst bath
3. exposed romex shall have protection from physical damage...under kitchen sink
4. D/W shall be hooked up and operational
5. OCPD on A/C is to large
ELE17-02039 Final6/28/20176/28/20176/28/2017 8:18:31 AMPPASS
Brent Phone #: ###-####...

ok to final
ELE17-02039 Permanent Service6/27/20176/28/20176/28/2017 8:18:12 AMAPASS
Brent Phone #: ###-####...

p/s ok to reconnect
ELE17-01872 Electrical Rough-In6/27/20176/28/20176/27/2017 2:05:26 PMACANC
Electrician: Preston Seay Phone #: ###-#### >> Inspection requested via web by Christian Kilpatrick Inspection cancelled from web by: Christian Kilpatrick