ELE17-02041
| Conference | 6/27/2017 | 6/28/2017 | 6/28/2017 2:17:39 PM | P | DONE |
|
|
Vehicle Inspection Pit Phone #: ###-#### Inspection requested via web by Kerri Hamilton Will need a area of classification by a licensed engineer to deem area for inspection and work to be done...
|
ELE17-01708
| Electrical Rough-In | 6/28/2017 | 6/28/2017 | 6/28/2017 1:55:43 PM | P | NR |
|
|
Conduit burial inspection so can backfill // Mark Phone #: ###-#### No registered journeyman and license is expired with State of Idaho. No ispection until resolved...
|
ELE17-01367
| Electrical Rough-In | 6/28/2017 | 6/28/2017 | 6/28/2017 1:45:06 PM | P | PASS |
|
|
We need an underground inspection please. Thank you, Dale. Phone #: ###-#### Inspection requested via web by Tom Jenkins Secondaries and 4" data only ok cover
|
ELE17-02032
| Final | 6/27/2017 | 6/28/2017 | 6/28/2017 1:44:18 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jose Guerrero Service change only final ok
|
ELE17-01204
| Final | 6/28/2017 | 6/28/2017 | 6/28/2017 12:12:13 PM | P | FAIL |
|
|
Rick Phone #: ###-#### 210.8 all 120v receptacles located within a garage shall be GFCI
|
ELE17-02048
| Electrical Rough-In | 6/27/2017 | 6/28/2017 | 6/28/2017 10:11:23 AM | A | PASS |
|
|
Need to inspect one small wall so they can cover. Access code on lock box is HCD. Any questions please give me a call at ###-####. Phone #: ###-#### Inspection requested via web by Warren Fry Pass through wall to kitchen only ok cover
|
ELE17-01452
| Final | 6/28/2017 | 6/28/2017 | 6/28/2017 9:40:39 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks GFCI protection for drinking fountain&shall be readily accessible Face plates required Feild identification needed in panelboard
|
ELE17-02043
| Temporary Service | 6/27/2017 | 6/28/2017 | 6/28/2017 8:52:01 AM | A | PASS |
|
|
Any issues plz let me know, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren t/s u/g n ok
|
ELE17-01066
| Final | 6/27/2017 | 6/28/2017 | 6/28/2017 8:45:49 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Matthew Hansen Bathroom receptacle shall be tamper resistant All receptacles shall be GFCI protected in a kitchen
|