FIR17-00275
| INSP-Sprinkler Rough-in | 6/28/2017 | 6/28/2017 | 6/28/2017 2:01:24 PM | P | PASS |
|
|
IBR only is ok to cover. The remaining piping will be installed later. No thrust block, mechanical restraint is being used.
|
FIR17-00235
| INSP-Final Inspection | 6/28/2017 | 6/28/2017 | 6/28/2017 1:29:14 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00635
| INSP-Final Inspection | 6/28/2017 | 6/28/2017 | 6/28/2017 1:28:57 PM | P | PASS |
|
|
permit finaled
|
BLD17-01048
| FIRE-Final Inspection | 6/27/2017 | 6/28/2017 | 6/28/2017 1:28:18 PM | P | FAIL |
|
|
Remove the thumb turn dead bolts from both restraunt doors, keyed is ok on the main entry/exit.
Repair the west side exit discharge light Repair the restruant emergency light Repair the stairwell emergency light
Provide fire extinguisher for basement Provide annual inspection for all extinguishers Provide inspection/certification for the hood suppression system
Contact plan review to verify that the restraunt door swing is acceptable.Plans show swing out but they only swing in.
|
BLD17-01785
| FIRE-Final Inspection | 6/27/2017 | 6/28/2017 | 6/28/2017 10:07:42 AM | A | PASS |
|
|
Life safety passed
|