ELE17-03734
| Conference | 6/27/2018 | 6/28/2018 | 6/28/2018 2:34:42 PM | P | NH |
|
|
Requesting a consultation with Daryl specifically to review the panel wall which failed inspection on June 21st. The General Contractor will be scheduling the plumbing inspector as well to review all possible solutions. Please provide 1/2 hour notice before arriving to site to ensure all parties are present. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Called contact and explained Chief Electrical Inspector is off thru end of week and should return July 2. I told I had a meeting with Chief about correction and he agreed shall be code compliant. If would still like to meet will have to wait until Monday when he returns.
|
ELE18-01691
| Permanent Service | 6/28/2018 | 6/28/2018 | 6/28/2018 2:19:00 PM | P | FAIL |
|
|
Von. Phone #: ###-#### Inspection requested via web by Sean DeLacy Located on back of liquor store. 110.24- Available fault current shall be posted prior to inspection with value and date calculated. 250.92(B)- Service equipment bonding, metal underground service lateral conduit shall both be bonded where they enter thru concentric knock outs.
|
ELE17-01549
| Final | 6/28/2018 | 6/28/2018 | 6/28/2018 1:49:38 PM | P | FAIL |
|
|
Please call Shane prior to inspection so he can meet you onsite. Phone #: ###-#### Inspection requested via web by Shawna Gates Corrections not completed. Must recall when complete.
|
ELE18-01092
| Final | 6/27/2018 | 6/28/2018 | 6/28/2018 12:14:21 PM | A | PASS |
|
|
garage code 2124 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
ELE17-03778
| Final | 6/27/2018 | 6/28/2018 | 6/28/2018 11:28:01 AM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Shane Lott North entrance TV power needs terminated, Checked customer service and misc receptacle locations in starbucks only. Contractor to call for final when 375 is back from vacation.
|
ELE18-01204
| Final | 6/27/2018 | 6/28/2018 | 6/28/2018 10:25:42 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
ELE18-01205
| Final | 6/27/2018 | 6/28/2018 | 6/28/2018 10:25:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
ELE18-02233
| Rough-In Permanent Service | 6/27/2018 | 6/28/2018 | 6/28/2018 9:13:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Wire coiled wall next to fireplace and for floor receptacle in basement ceiling center bed near smoke. Attic boxes associated with furnace trimmed at rough in. Rough in ok cover p/s o/h n ok
|