Inspections for the day of: Thursday, June 28, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03734 Conference6/27/20186/28/20186/28/2018 2:34:42 PMPNH
Requesting a consultation with Daryl specifically to review the panel wall which failed inspection on June 21st. The General Contractor will be scheduling the plumbing inspector as well to review all possible solutions. Please provide 1/2 hour notice before arriving to site to ensure all parties are present. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Called contact and explained Chief Electrical Inspector is off thru end of week and should return July 2. I told I had a meeting with Chief about correction and he agreed shall be code compliant. If would still like to meet will have to wait until Monday when he returns.
ELE18-01691 Permanent Service6/28/20186/28/20186/28/2018 2:19:00 PMPFAIL
Von. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Located on back of liquor store.
110.24- Available fault current shall be posted prior to inspection with value and date calculated.
250.92(B)- Service equipment bonding, metal underground service lateral conduit shall both be bonded where they enter thru concentric knock outs.
ELE17-01549 Final6/28/20186/28/20186/28/2018 1:49:38 PMPFAIL
Please call Shane prior to inspection so he can meet you onsite. Phone #: ###-#### Inspection requested via web by Shawna Gates
Corrections not completed. Must recall when complete.
ELE18-01092 Final6/27/20186/28/20186/28/2018 12:14:21 PMAPASS
garage code 2124 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE17-03778 Final6/27/20186/28/20186/28/2018 11:28:01 AMAPART
Phone #: ###-#### Inspection requested via web by Shane Lott
North entrance TV power needs terminated, Checked customer service and misc receptacle locations in starbucks only. Contractor to call for final when 375 is back from vacation.
ELE18-01204 Final6/27/20186/28/20186/28/2018 10:25:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE18-01205 Final6/27/20186/28/20186/28/2018 10:25:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
ELE18-02233 Rough-In Permanent Service6/27/20186/28/20186/28/2018 9:13:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Wire coiled wall next to fireplace and for floor receptacle in basement ceiling center bed near smoke. Attic boxes associated with furnace trimmed at rough in.
Rough in ok cover p/s o/h n ok