Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01884 Electrical Rough-In6/29/20056/29/20056/29/2005 4:00:23 PMPPASS
Scheduled by a contractor via Hello! on 6/29/2005 at 9:05:11 AM. Contact: ###-####. cielings ok
ELE05-02309 Permanent Service6/29/20056/29/20056/29/2005 3:52:17 PMPFAIL
###-#### - harvey Note: 100 ump cor. posted 200.6 no ID 6 or smaller, 250.92(A)(3) bond both ends raceway for GEC,334.46 bushings for rigid, 408.36(F),408.4 sub panel
ELE05-01501 Final6/29/20056/29/20056/29/2005 2:55:33 PMPPASS
Scheduled by a contractor via Hello! on 6/29/2005 at 9:37:58 AM. Contact: ###-####. ok
ELE05-02307 Electrical Rough-In6/29/20056/29/20056/29/2005 2:14:51 PMPFAIL
dee bolds - ###-#### Note: please call 1/2 hr prior to inspection met owner partial correction posted, not ready, and 90% of work inviolation of N E C, 314.43,16, 210.52(ABCDEF),210.70, 300.4, complete all makeup, replace all boxes with broken clamps cow
ELE05-02272 Temporary Service6/29/20056/29/20056/29/2005 12:29:48 PMPPASS
###-#### - hp t/s u/g new ok
ELE05-01977 Electrical Rough-In6/28/20056/29/20056/29/2005 11:02:39 AMAPASS
Please contact Matt, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ceilings ok
ELE05-02133 Final6/28/20056/29/20056/29/2005 10:38:04 AMAPASS
after 9 please////jason; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok no card
ELE05-01482 Final6/28/20056/29/20056/29/2005 10:24:09 AMAFAIL
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted called left message fee due, 110.3 shall not alter panel reinstall neutral bus, 200.6 shall not ID 6or smaller neutral,, 250.8 no SMS for grds or bonds equip. grd bus
ELE05-02283 Electrical Rough-In6/28/20056/29/20056/29/2005 10:19:46 AMAPASS
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
r/i ok fire job
ELE04-02864 Final6/28/20056/29/20056/29/2005 10:19:13 AMAFAIL
Internet Inspection Request from: Radon Elaina notice posted contractor was told once before to set up meeting with inspector called contractor
ELE05-01170 Electrical Rough-In6/28/20056/29/20056/29/2005 8:42:08 AMAPASS
ceiling cover//dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok