ELE06-02446
| Permanent Service | 6/29/2006 | 6/29/2006 | 6/29/2006 4:30:47 PM | P | PASS |
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s u/g n ok
|
ELE06-00511
| Final | 6/29/2006 | 6/29/2006 | 6/29/2006 3:49:57 PM | P | NR |
|
|
any questions please call Chris Hill; Phone #: ###-#### Internet Inspection Request from: Jeff Radford #370, 315, & 412 all met on job, talked to elect and reviewed what was done. Open items to be finished are no tie wraps on light cord, strap conduit over panels, put on covers, label breakers,remove pipe over panel in basement, phone wire to elev cabinet to be correct, label elevator, verify furniture labels and power supply cords and interconnect for labelled assembly, verify power poles for raceway, verify furnitue power distribution requirements, verify if breakers need to be 3 pole for furniture, update permit if wire in power for furniture, ensure occupancy sensors work in baths, verify type of furniture , covers shall be put on lv boxes
|
ELE06-01988
| Electrical Rough-In | 6/29/2006 | 6/29/2006 | 6/29/2006 3:21:50 PM | P | PASS |
|
|
u/g for conduits only ok to vover
|
ELE06-01988
| Rough-In Permanent Service | 6/29/2006 | 6/29/2006 | 6/29/2006 3:20:36 PM | P | CANC |
|
|
Underground Inspection Pool Alt Phones ###-#### (Rick) or ###-#### ( Kelly ); Phone #: ###-#### Internet Inspection Request from: Cathy Felin wrong type inspection request
|
ELE06-02442
| Final | 6/29/2006 | 6/29/2006 | 6/29/2006 2:22:13 PM | P | FAIL |
|
|
We installed 2 new 20 amp 120 volt circuits to feed 5 new receptacles above the t-bar ceiling in the following rooms:Theory rooms #1,#2,#7, & Labs #2,#4. This is at ITT Technical Institute, ask for guideance at the front desk.Jman/Jason ###-####.Thanks!!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell called told correction notice 400.8(2) no flexible cord shall be run thru ceiling
|
ELE06-02429
| Electrical Rough-In | 6/28/2006 | 6/29/2006 | 6/29/2006 1:36:16 PM | P | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton called contr, needs plans, make-up, 1 1/4", mud rings. said to call when ready
|
ELE06-00457
| Final | 6/28/2006 | 6/29/2006 | 6/29/2006 11:51:06 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok to final, signed occ card
|
ELE06-00456
| Final | 6/28/2006 | 6/29/2006 | 6/29/2006 9:55:14 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS ok to final, no struct card on site to sign
|
ELE06-01194
| Final | 6/28/2006 | 6/29/2006 | 6/29/2006 9:36:05 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Eric Shaner ok to final
|
ELE06-01922
| Final | 6/28/2006 | 6/29/2006 | 6/29/2006 9:00:07 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jari Rivers called left message, left survey, nec 312.5 all conductors entering enclosures shall have abrasion protection
|
ELE06-01195
| Final | 6/28/2006 | 6/29/2006 | 6/29/2006 8:51:23 AM | A | PASS |
|
|
High Desert Harley Davidson signage; Phone #: ###-#### Internet Inspection Request from: Eric Shaner ok to final
|
ELE06-02301
| Electrical Rough-In | 6/28/2006 | 6/29/2006 | 6/29/2006 8:25:42 AM | A | PASS |
|
|
Please contact Dan Wilken, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called left message, left survey, nec 330.30(B) mc cable shall be secured within 12" of every box, 725.3(B) accessible portion of abandoned cl2,cl3, and pltc cable shall be removed, BCC all make-up shall be done
|