Inspections for the day of: Thursday, June 29, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00425 INSP-Sprinkler Rough-in/Hydro6/27/20066/29/20066/29/2006 4:07:02 PMPPART
Cover inspection for the hotel lobby hard lid entry area is good for cover.
FIR06-00128 INSP-Final Inspection6/29/20066/29/20066/29/2006 3:49:04 PMPFAIL
Need to provide a pressure relief valve for the grid system in the basement per NFPA 13, provide head cages at the exposed upright heads under stairs, one room marked "closet B108" in the basement is missing sprinkler coverage, provide as-builts reflecting actual field install at the first floor lobby where drop ceilings have been deleted and wall layouts changed as previously requested, need to provide playpipe to enable accurate testing of forward flow through the FDC- see review comments. Inspection concluded at this time due to the number of correction items noted as final field inspection is not designed for punch list or quality control purposes on behalf of the contractor.
FIR05-00659 INSP-Sprinkler Rough-in/Hydro6/29/20066/29/20066/29/2006 3:13:18 PMPPART
OH rough-in at the west office area appears acceptable as installed, however the installation does not match approved plans and will require plans reflecting actual field installation prior to final.
FIR06-00293 INSP-Sprinkler Rough-in/Hydro6/27/20066/29/20066/29/2006 2:32:32 PMAPASS
The remainder of OH rough-in passed inspection.
FIR06-00392 INSP-Sprinkler Rough-in/Hydro6/28/20066/29/20066/29/2006 2:31:45 PMAPASS
OH rough-in passed inspection.
BLD06-01340 FIRE-Final Inspection6/28/20066/29/20066/29/2006 12:19:57 PMAPASS
Fire life safety is satisfactory, inspection passed.
FIR06-00454 INSP-Final Inspection6/28/20066/29/20066/29/2006 12:19:03 PMAPASS
Fire alarm work passed final field inspection.
FIR06-00343 INSP-Final Inspection6/28/20066/29/20066/29/2006 12:18:09 PMAPASS
Fire sprinkler passed final inspection, permit finaled.
FIR05-00033 INSP-Final Inspection6/26/20066/29/20066/29/2006 11:25:55 AMAFAIL
Tested all duct detectors today, one detector(device 30) in the basement failed to function, one detector on the 2nd floor will need to be relocated as it is upstream of a return grill, need to change descriptor of one detector location at the cafe ole office area. Noted that the SD's located adjacent to the atrium in several locations will not function as installed due to open ceiling beam obstructions greater than 12" in depth.
FIR05-00764 INSP-Final Inspection6/28/20066/29/20066/29/2006 9:22:29 AMAPASS
Required corrections have been completed, final alarm inspection passed.