Inspections for the day of: Friday, June 29, 2007.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01624 Electrical Rough-In6/29/20076/29/20076/29/2007 3:25:17 PMPPASS
Scheduled by a contractor via Hello! on 6/29/2007 at 9:33:24 AM. Contact: ###-####. ok to cover u/g anop, imc to therapy areas from elect room
ELE06-02392 Final6/29/20076/29/20076/29/2007 2:50:32 PMPPASS
randy - parking lot lights; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang called contr, no occupancy card, ok to final
ELE07-00201 Permanent Service6/29/20076/29/20076/29/2007 2:28:38 PMPFAIL
nicki Phone #: ###-#### met owner, left corr notice, nec 250.52(A)(1) shall connect metal water pipe as grounding electrode,250.53(D)(2) shall provide supplemental grounding electrode per 250.56, 110.3(B) shall use listed clamps, 110.12(C) there shall be no deteriorated parts, BCC shall provide minimum 2" mast with proper clearances, told owner several options for service, he has to install and we will inspect
ELE07-00271 Electrical Rough-In6/29/20076/29/20076/29/2007 1:43:23 PMPPASS
rough in front canopy & ceiling grid. Call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ceiling and front canopy ok to cover
ELE07-02237 Electrical Rough-In6/29/20076/29/20076/29/2007 1:06:06 PMPPASS
JACK Phone #: ###-#### corrections made, ric ok
ELE07-02328 Electrical Rough-In6/28/20076/29/20076/29/2007 12:30:42 PMPCANC
andy; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang wrong type request, see p/s
ELE07-02328 Permanent Service6/29/20076/29/20076/29/2007 12:30:15 PMPPASS
andy; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang p/s o/h rec ok
ELE07-01807 Final6/28/20076/29/20076/29/2007 11:46:02 AMAPASS
damon - pls call 30 mins prior; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang ok to final, signed occ card
ELE07-02211 Rough-In Permanent Service6/28/20076/29/20076/29/2007 11:01:15 AMAFAIL
Shane Vanleuven / inspect for service and Mech. room. Phone #: ###-#### Internet Inspection Request from: Debby Ellis called left corr notice, 334.30 nm cable shall be strapped within 12" of box, 362.26 ent shall not have over 360 degree bends, 250.52(A)(1) shall use water pipe within 5' of entering building for grounding electrode to service, 110.14(A) ground clamp shall be tight, BCC old exst gnd rod shall be abandoned or used with proper clamp
ELE07-00836 Rough-In Permanent Service6/28/20076/29/20076/29/2007 10:34:12 AMAPASS
roger - underground service; Phone #: ###-#### Internet Inspection Request from: Victoria Apatang u/g to shop ok to cover, p/s u/g rec ok
ELE07-00573 Electrical Rough-In6/29/20076/29/20076/29/2007 10:10:37 AMAPART
Scheduled by a contractor via Hello! on 6/29/2007 at 6:38:47 AM. Contact: ###-####. ok to pour cnds over west cells for ceiling cover
ELE07-01624 Electrical Rough-In6/28/20076/29/20076/29/2007 9:34:24 AMACANC
Scheduled by a contractor via Hello! on 6/28/2007 at 2:59:12 PM. Contact: ###-####. see conf
ELE07-01624 Conference6/29/20076/29/20076/29/2007 9:31:55 AMADONE
Scheduled by a contractor via Hello! on 6/28/2007 at 2:59:12 PM. Contact: ###-####. talked to contr about spacing u/g and supporting
ELE07-01301 Final6/29/20076/29/20076/29/2007 9:18:08 AMAPASS
Scheduled by a contractor via Hello! on 6/29/2007 at 6:04:08 AM. Contact: ###-####. called, ok to final
ELE07-01303 Final6/29/20076/29/20076/29/2007 9:17:31 AMAPASS
Scheduled by a contractor via Hello! on 6/29/2007 at 6:06:28 AM. Contact: ###-####. called, ok to final
ELE07-02331 Final6/28/20076/29/20076/29/2007 8:35:22 AMAPASS
ROBERT ###-#### called contr about jacketing, stapling nm on edge, ok to final
ELE07-02331 Electrical Rough-In6/29/20076/29/20076/29/2007 8:34:45 AMAPASS
ROBERT ###-#### ric ok
ELE07-02330 Final6/28/20076/29/20076/29/2007 8:33:21 AMAPASS
ROBERT ###-#### ok to final
ELE07-02330 Electrical Rough-In6/29/20076/29/20076/29/2007 8:33:11 AMAPASS
ROBERT ###-#### ric ok
ELE07-01257 Electrical Rough-In6/25/20076/29/20076/29/2007 8:00:58 AMACANC
Gene ###-####. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson wrong type request, see final