FIR06-00007
| INSP-Alarm Testing | 6/27/2007 | 6/29/2007 | 7/2/2007 10:22:20 AM | A | FAIL |
|
|
SD's as installed in the electrical room, comm. room, and loading dock area do not meet spacing requirements due to structural beam blockage, missing one SD at a vestibule, visible notification is blocked at some areas in the pyro lab, duct detectors and vesdas tested okay on the first floor, noted corrections from the previous visit have been completed.
|
FIR06-00959
| INSP-Sprinkler Rough-in | 6/27/2007 | 6/29/2007 | 7/2/2007 10:16:08 AM | A | PART |
|
|
Inspection for the underfloor fire sprinklers is acceptable, noted one branchline is not tied in at this time.
|
FIR07-00244
| INSP-Sprinkler Rough-in | 6/27/2007 | 6/29/2007 | 6/29/2007 1:22:08 PM | A | FAIL |
|
|
Overspaced heads, one missing upright, missing retaining straps for hangers at several locations, some areas as red lined on plans are not yet completed, install is not approved for cover until corrections are made and re-inspected.
|
FIR07-00357
| INSP-Sprinkler Rough-in | 6/27/2007 | 6/29/2007 | 6/29/2007 1:19:14 PM | A | PART |
|
|
OH rough-in is okay for cover except at areas as noted on approved plans- one hanger needs to be added, one retaining strap is not attatched.
|
FIR07-00499
| INSP-Conference | 6/29/2007 | 6/29/2007 | 6/29/2007 12:40:20 PM | P | DONE |
|
|
On site conference regarding notification device locations at the common corridor SE and NE sides.
|
FIR07-00573
| INSP-Conference | 6/28/2007 | 6/29/2007 | 6/29/2007 10:58:03 AM | A | DONE |
|
|
On site visit to discuss locations of manual pull stations for activation of the hood suppression systems, agreed to positions as indicated.
|
BLD06-01488
| FIRE-Final Inspection | 6/28/2007 | 6/29/2007 | 6/29/2007 10:22:33 AM | A | FAIL |
|
|
Need to provide approved plans on site for review.
|
FIR07-00269
| INSP-Final Inspection | 6/27/2007 | 6/29/2007 | 6/29/2007 12:00:00 AM | A | CANC |
|
|
ed - 6:00 am Phone #: ###-####
|