Inspections for the day of: Thursday, June 29, 2017.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-00722 FIRE-Final Inspection6/28/20176/29/20176/29/2017 1:08:06 PMPPASS
life safety passed
FIR17-00304 INSP-Sprinkler Rough-in6/29/20176/29/20176/29/2017 12:59:37 PMPDONE
Adam and I spoke about the two heads off of a single outlet. Hydraulic calculations will be required or piping will need to match plans.
BLD17-01941 FIRE-Final Inspection6/27/20176/29/20176/29/2017 11:49:21 AMAPASS
life safety passed
BLD17-02045 FIRE-Final Inspection6/28/20176/29/20176/29/2017 11:08:09 AMAPASS
life safety passed
BLD16-04520 FIRE-Final Inspection6/28/20176/29/20176/29/2017 10:59:28 AMAPASS
life safety passed
BLD17-01670 FIRE-Final Inspection6/28/20176/29/20176/29/2017 10:16:21 AMAPART
A temporary occupancy is ok for 30 days so that the fire alarm notification can be extended into this remodeled space.

Sid Phone #: ###-####
BLD16-01848 FIRE-Final Inspection6/28/20176/29/20176/29/2017 10:14:35 AMAFAIL
Provide verification of evacution guides as discussed, provide closers on exterior doors, provide 3' minimum clearance from smoke alarms to bathroom doors with tub or shower.
BLD16-01847 FIRE-Final Inspection6/28/20176/29/20176/29/2017 10:14:19 AMAFAIL
Provide verification of evacution guides as discussed, provide closers on exterior doors, provide 3' minimum clearance from smoke alarms to bathroom doors with tub or shower.
BLD16-01850 FIRE-Final Inspection6/28/20176/29/20176/29/2017 10:14:04 AMAFAIL
Provide verification of evacution guides as discussed, provide closers on exterior doors, provide 3' minimum clearance from smoke alarms to bathroom doors with tub or shower.
BLD16-01849 FIRE-Final Inspection6/28/20176/29/20176/29/2017 10:13:44 AMAFAIL
Provide verification of evacution guides as discussed, provide closers on exterior doors, provide 3' minimum clearance from smoke alarms to bathroom doors with tub or shower.
BLD17-01495 FIRE-Final Inspection6/28/20176/29/20176/29/2017 10:11:06 AMAPASS
life safety passed
FIR17-00339 INSP-Final Inspection6/28/20176/29/20176/29/2017 8:17:26 AMAPASS
Permit finaled