FIR04-00055
| FIR-Aging Inspection | 6/3/2004 | 6/3/2004 | 6/4/2004 12:00:00 AM | | PASS |
|
|
Talked to Mark of Simplex and the work is in progress and expects to have this ready in few weeks 6/4/2004 10:59:30 AM
|
FIR02-00359
| INSP-Final Inspection | 6/1/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 6/1/2004 at 7:57:32 AM. Contact: ###-####. AV12-3 not working; need to test new tamper/flow; need as-builts to verify changes made to all NAC's as they don't match plans; NAC 2 circuits wired backwards at panel; labels on AV's not correct 6/3/2004 11:52:23 AM
|
BLD03-01267
| FIRE-Final Inspection | 6/2/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/2/2004 at 7:52:53 AM. Contact: ###-####.
|
BLD04-00510
| FIRE-Sprinkler Rough-in | 6/2/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | A | NR |
|
|
Scheduled by a contractor via Hello! on 6/2/2004 at 7:59:20 AM. Contact: ###-####. will need sprinkler plans for new grid ceiling to install drops 6/3/2004 11:50:00 AM
|
FIR03-00448
| INSP-Sprinkler Rough-in/Hydro | 6/2/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | A | PASS |
|
|
24 hour air test okay 6/3/2004 11:02:50 AM
|
FIR04-00096
| INSP-Final Inspection | 6/3/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | A | PASS |
|
|
|
FIR04-00293
| INSP-Final Inspection | 6/2/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | A | PASS |
|
|
darren; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
BLD02-01157
| FIRE-Final Inspection | 6/2/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | A | PASS |
|
|
Bob; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes All items for life safety okay; awaiting alarm sprinkler monitoring 6/3/2004 10:48:10 AM
|
BLD03-01424
| FIRE-Final Inspection | 6/2/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | A | NH |
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes 6/4/2004 2:39:28 Stopped by on 6/3 and nobody home; called again on 6/4 and left message; will reschedule for 6/7 6/4/2004 3:22:18 PM
|
FIR04-00269
| INSP-Final Inspection | 5/28/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 5/28/2004 at 5:04:24 PM. Contact: ###-####.
|
MIS04-00117
| FIR-Final | 6/3/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | PASS |
|
|
|
FIR04-00233
| INSP-Final Inspection | 6/3/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | PART |
|
|
The system is complete except for the new anti-freeze loop on the terrace; will need to test the tampers when completed; Knox box has been ordered 6/3/2004 4:27:16 PM
|
BLD04-00038
| FIRE-Final Inspection | 6/3/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | PART |
|
|
Phase I completed - the terrace isn't ready to occupy but the rest of the area is okay to occupy 6/3/2004 4:28:16 PM
|
FIR04-00218
| INSP-Sprinkler Rough-in/Hydro | 6/3/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | PASS |
|
|
UG hydro okay 6/3/2004 4:13:16 PM
|
FIR04-00179
| INSP-Sprinkler Rough-in | 6/2/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | PART |
|
|
Contact: Charles - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Need to complete the anti-freeze loop when the terrace is ready 6/3/2004 4:18:52 PM
|
BLD03-02393
| FIRE-Final Inspection | 6/3/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | PASS |
|
|
cameron; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Pocket doors were removed 6/3/2004 2:44:12 PM
|
FIR04-00218
| INSP-Supply line flush | 6/3/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | FAIL |
|
|
supply line hydro inspection please///sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore hydro lost 7 psi 6/3/2004 1:49:42 PM
|
BLD01-02537
| BLD-Aging Inspection | 6/3/2004 | 6/3/2004 | 6/3/2004 12:00:00 AM | P | NR |
|
|
|