Inspections for the day of: Thursday, June 3, 2004.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00055 FIR-Aging Inspection6/3/20046/3/20046/4/2004 12:00:00 AM PASS
Talked to Mark of Simplex and the work is in progress and expects to have this ready in few weeks 6/4/2004 10:59:30 AM
FIR02-00359 INSP-Final Inspection6/1/20046/3/20046/3/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 6/1/2004 at 7:57:32 AM. Contact: ###-####. AV12-3 not working; need to test new tamper/flow; need as-builts to verify changes made to all NAC's as they don't match plans; NAC 2 circuits wired backwards at panel; labels on AV's not correct 6/3/2004 11:52:23 AM
BLD03-01267 FIRE-Final Inspection6/2/20046/3/20046/3/2004 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 6/2/2004 at 7:52:53 AM. Contact: ###-####.
BLD04-00510 FIRE-Sprinkler Rough-in6/2/20046/3/20046/3/2004 12:00:00 AMANR
Scheduled by a contractor via Hello! on 6/2/2004 at 7:59:20 AM. Contact: ###-####. will need sprinkler plans for new grid ceiling to install drops 6/3/2004 11:50:00 AM
FIR03-00448 INSP-Sprinkler Rough-in/Hydro6/2/20046/3/20046/3/2004 12:00:00 AMAPASS
24 hour air test okay 6/3/2004 11:02:50 AM
FIR04-00096 INSP-Final Inspection6/3/20046/3/20046/3/2004 12:00:00 AMAPASS
FIR04-00293 INSP-Final Inspection6/2/20046/3/20046/3/2004 12:00:00 AMAPASS
darren; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
BLD02-01157 FIRE-Final Inspection6/2/20046/3/20046/3/2004 12:00:00 AMAPASS
Bob; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes All items for life safety okay; awaiting alarm sprinkler monitoring 6/3/2004 10:48:10 AM
BLD03-01424 FIRE-Final Inspection6/2/20046/3/20046/3/2004 12:00:00 AMANH
Steve; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes 6/4/2004 2:39:28 Stopped by on 6/3 and nobody home; called again on 6/4 and left message; will reschedule for 6/7 6/4/2004 3:22:18 PM
FIR04-00269 INSP-Final Inspection5/28/20046/3/20046/3/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 5/28/2004 at 5:04:24 PM. Contact: ###-####.
MIS04-00117 FIR-Final6/3/20046/3/20046/3/2004 12:00:00 AMPPASS
FIR04-00233 INSP-Final Inspection6/3/20046/3/20046/3/2004 12:00:00 AMPPART
The system is complete except for the new anti-freeze loop on the terrace; will need to test the tampers when completed; Knox box has been ordered 6/3/2004 4:27:16 PM
BLD04-00038 FIRE-Final Inspection6/3/20046/3/20046/3/2004 12:00:00 AMPPART
Phase I completed - the terrace isn't ready to occupy but the rest of the area is okay to occupy 6/3/2004 4:28:16 PM
FIR04-00218 INSP-Sprinkler Rough-in/Hydro6/3/20046/3/20046/3/2004 12:00:00 AMPPASS
UG hydro okay 6/3/2004 4:13:16 PM
FIR04-00179 INSP-Sprinkler Rough-in6/2/20046/3/20046/3/2004 12:00:00 AMPPART
Contact: Charles - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Need to complete the anti-freeze loop when the terrace is ready 6/3/2004 4:18:52 PM
BLD03-02393 FIRE-Final Inspection6/3/20046/3/20046/3/2004 12:00:00 AMPPASS
cameron; Phone #: ###-#### Internet Inspection Request from: Barbara Moore Pocket doors were removed 6/3/2004 2:44:12 PM
FIR04-00218 INSP-Supply line flush6/3/20046/3/20046/3/2004 12:00:00 AMPFAIL
supply line hydro inspection please///sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore hydro lost 7 psi 6/3/2004 1:49:42 PM
BLD01-02537 BLD-Aging Inspection6/3/20046/3/20046/3/2004 12:00:00 AMPNR