Inspections for the day of: Friday, June 3, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01884 Electrical Rough-In6/3/20056/3/20056/3/2005 2:40:48 PMPPART
Scheduled by a contractor via Hello! on 6/3/2005 at 11:08:09 AM. Contact: ###-####.ceilings ok
ELE05-01931 Electrical Rough-In6/2/20056/3/20056/3/2005 2:02:26 PMPPART
ANY QUESTIONS PLEASE CALL ED SCHALLOCK; Phone #: ###-#### Internet Inspection Request from: Jeff Radford u/f for p/s and east end parking lot u/g 2 locations
ELE05-00229 Final6/3/20056/3/20056/3/2005 1:43:06 PMPPASS
pat; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok card signed
ELE05-00976 Final6/3/20056/3/20056/3/2005 1:42:44 PMPNH
pat; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa no access called
ELE05-01353 Final6/3/20056/3/20056/3/2005 12:52:44 PMPPASS
pat; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok no card
ELE05-01938 Temporary Service6/3/20056/3/20056/3/2005 11:46:52 AMPPASS
rick ###-#### t/s u/g new ok
ELE05-00459 Final6/2/20056/3/20056/3/2005 10:34:17 AMAFAIL
henry; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa cor. posted called needs instructions for j-tub, is paddle fan listed for outdoors, 250.148 grd metal boxes island, 300.10&314.3 no metal raceways in plastic boxes mech. rm furnace, 200.6&7 ID white in cables as phase where used as, 404.4 WP for outdoor switches, 408.4 label panels correctly, no power to recept front entry, wire DW
ELE04-03719 Final6/2/20056/3/20056/3/2005 9:55:45 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertsonok
ELE05-01917 Electrical Rough-In6/2/20056/3/20056/3/2005 8:54:46 AMAPART
morrey; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles shall not use plastic boxes with metal raceway, needs connectors for romex at boxes, shall not switch neutral, splice all grds
ELE05-01920 Electrical Rough-In6/2/20056/3/20056/3/2005 8:26:16 AMAPART
Scheduled by a contractor via Hello! on 6/2/2005 at 1:19:03 PM. Contact: ###-####. u/g for center runway running N and S west end runway, and new vault