Inspections for the day of: Friday, June 3, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-02245 BLD-Aging Inspection6/3/20056/3/20056/6/2005 2:43:41 PM DONE
I spoke with Fred Bartlett ###-####, who is now the new GM for the facility, and discussed the actions required to final this permit. He will obtain the proper documents and call for inspection when ready.
BLD05-00094 FIRE-Final Inspection6/2/20056/3/20056/3/2005 1:54:32 PMAPASS
Fire life safety finaled.
FIR04-00764 INSP-Sprinkler Rough-in/Hydro6/2/20056/3/20056/3/2005 12:07:57 PMAPART
Overhead rough in passed inspection. Hydrostatic test on AG pipe also passed inspection.
BLD04-00313 FIRE-Final Inspection6/2/20056/3/20056/3/2005 11:12:12 AMAFAIL
NO storage allowed in cellar, per plan it is a non-usable area, install fire ext. with current tag no higher than 48" AFF, provide approved door hardware at all means of egress and exits, provide building street address with numbers min. 4" high. NO occupancy allowed until permits are finaled.
FIR05-00296 INSP-Final Inspection6/2/20056/3/20056/3/2005 8:30:35 AMAPASS
Fire alarm finaled.
FIR05-00251 INSP-Final Inspection6/3/20056/3/20056/3/2005 12:00:00 AMPPASS
Fire sprinkler finaled.
BLD05-00894 FIRE-Final Inspection6/3/20056/3/20056/3/2005 12:00:00 AMPFAIL
Need to relocate fire extinguisher to a normal path of travel.
FIR05-00152 INSP-Sprinkler Rough-in/Hydro6/3/20056/3/20056/3/2005 12:00:00 AMPPART
Underground supply line OK to cover up to installed point just past vault.
BLD05-00894 FIRE-Final Inspection6/3/20056/3/20056/3/2005 12:00:00 AMPPASS
Fire life safety finaled.
FIR05-00258 INSP-Sprinkler Rough-in/Hydro6/3/20056/3/20056/3/2005 12:00:00 AMPPART
End 24 hr. air test of dry system overhead piping. Test passed inspection.