Inspections for the day of: Friday, June 3, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD04-00870 FIRE-Final Inspection6/2/20056/3/20056/3/2005 4:23:42 PMAPASS
fire life safety finaled
FIR04-00390 INSP-Final Inspection6/3/20056/3/20056/3/2005 4:22:49 PMPPASS
fire sprinkler finaled
FIR05-00241 INSP-Final Inspection6/3/20056/3/20056/3/2005 4:13:16 PMPPASS
Fire sprinkler finaled
FIR05-00249 INSP-Final Inspection6/2/20056/3/20056/3/2005 3:19:42 PMPFAIL
Need to install the 15cd strobe outside of the records room as shown on the approved plans and retest the notification circuit.
BLD04-02965 FIRE-Final Inspection6/2/20056/3/20056/3/2005 3:18:35 PMAFAIL
Need indicator for the lock at the main exit. No racking has been installed. Need suite number.
BLD05-00656 FIRE-Final Inspection6/2/20056/3/20056/3/2005 3:15:30 PMAFAIL
Electrician has not completed the installation of the emergency lights, exit signs and exit discharge lights. Cubicle layout has changed. I went over a modified layout of the exit signs with the electrician. Still need suite numbers.
FIR05-00217 INSP-Sprinkler Rough-in/Hydro6/3/20056/3/20056/3/2005 2:04:05 PMPPART
See city approved plans for location where wet system can be covered as of 6/3/05.
FIR05-00259 INSP-Sprinkler Rough-in/Hydro6/2/20056/3/20056/3/2005 12:04:49 PMAFAIL
Plans on job site are only have partial approvals. Updated plans are not on site. Could not do hydro because guage only showed 180lbs of pressure. No inspection done.
BLD04-01711 FIRE-Final Inspection6/2/20056/3/20056/3/2005 11:30:13 AMAPASS
fire life safety finaled
BLD04-00556 FIRE-Final Inspection5/31/20056/3/20056/3/2005 10:19:20 AMAFAIL
Door hardware on the main exit is not approved. If keyed lock is to remain an indicator must be provided with a sticker above the door. See fire review comments note #4
BLD05-00057 FIRE-Final Inspection6/2/20056/3/20056/3/2005 8:47:54 AMAFAIL
Remove manual flush bolts. See IFC 1008.1.8.4 and provide approved door hardware on all doors. See IFC 1008.1.8 and 1008.1.8.1
FIR05-00087 INSP-Final Inspection6/3/20056/3/20056/3/2005 12:00:00 AMPPASS
Fire sprinkler finaled
BLD00-03000 FIRE-Final Inspection6/3/20056/3/20056/3/2005 12:00:00 AMPPASS
Fire life safety finaled. Engineer and I measured hammerhead for fire dept turn around and it passed.
BLD04-02947 FIRE-Final Inspection6/1/20056/3/20056/2/2005 11:07:52 AMAPASS
life safety finaled