Inspections for the day of: Tuesday, June 3, 2008.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01654 FIRE-Final Inspection6/3/20086/3/20086/4/2008 11:55:12 AMPDEFR
Duplicate inspection request.
FIR07-00702 INSP-Final Inspection6/2/20086/3/20086/3/2008 9:15:54 PMADEFR
cole Phone #: ###-####
FIR08-00164 INSP-Sprinkler Rough-in6/3/20086/3/20086/3/2008 9:13:35 PMPPART
UG fire suply line installation appears satisfactory however the city stamped drawings and documents were not on site at the time of inspection per condition of the permit, will need to verify plans match install prior to final approval.
FIR08-00336 INSP-Sprinkler Rough-in6/3/20086/3/20086/3/2008 9:07:57 PMPPART
OH sprinkler system modifications at the tenant remodel area are acceptable, noted three locations on approved drawings where beam clamps have been installed and fireproofing will need to be repaired.
FIR07-00935 INSP-Sprinkler Rough-in5/30/20086/3/20086/3/2008 9:03:17 PMPPART
1st and 2nd floor south offices OH rough-in is approved for cover with the exception of one missing EQ brace at the 2nd floor 3" main east side last piece.
FIR08-00259 INSP-Final Inspection6/2/20086/3/20086/3/2008 12:47:29 PMAFAIL
First floor elevator lobby smoke detector failed to initiate alternate floor recall, no other items tested at this time.
FIR08-00348 INSP-Final Inspection6/2/20086/3/20086/3/2008 12:21:59 PMAFAIL
Project is not ready for final at this time due to finishes and construction underway-missng escutcheons, paint masking, etc.
FIR07-00663 INSP-Sprinkler Rough-in/Hydro6/2/20086/3/20086/3/2008 12:20:15 PMAPART
Overhead hydrostatic testing completed satisfactory for the new system piping.
FIR08-00163 INSP-Sprinkler Rough-in6/2/20086/3/20086/3/2008 12:19:04 PMAPART
Remainder of UG fire supply approved for cover including thrust blocks and ductile riser.
FIR08-00132 FIR-Aging Inspection6/3/20086/3/20086/3/2008 11:53:13 AM DONE
Work in progress
FIR08-00180 INSP-Final Inspection5/30/20086/3/20086/2/2008 7:49:04 AMPCANC
Scheduled by a contractor via Hello! on 5/30/2008 at 4:48:42 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jun 2 2008 7:49AM.