BLD07-01654
| FIRE-Final Inspection | 6/3/2008 | 6/3/2008 | 6/4/2008 11:55:12 AM | P | DEFR |
|
|
Duplicate inspection request.
|
FIR07-00702
| INSP-Final Inspection | 6/2/2008 | 6/3/2008 | 6/3/2008 9:15:54 PM | A | DEFR |
|
|
cole Phone #: ###-####
|
FIR08-00164
| INSP-Sprinkler Rough-in | 6/3/2008 | 6/3/2008 | 6/3/2008 9:13:35 PM | P | PART |
|
|
UG fire suply line installation appears satisfactory however the city stamped drawings and documents were not on site at the time of inspection per condition of the permit, will need to verify plans match install prior to final approval.
|
FIR08-00336
| INSP-Sprinkler Rough-in | 6/3/2008 | 6/3/2008 | 6/3/2008 9:07:57 PM | P | PART |
|
|
OH sprinkler system modifications at the tenant remodel area are acceptable, noted three locations on approved drawings where beam clamps have been installed and fireproofing will need to be repaired.
|
FIR07-00935
| INSP-Sprinkler Rough-in | 5/30/2008 | 6/3/2008 | 6/3/2008 9:03:17 PM | P | PART |
|
|
1st and 2nd floor south offices OH rough-in is approved for cover with the exception of one missing EQ brace at the 2nd floor 3" main east side last piece.
|
FIR08-00259
| INSP-Final Inspection | 6/2/2008 | 6/3/2008 | 6/3/2008 12:47:29 PM | A | FAIL |
|
|
First floor elevator lobby smoke detector failed to initiate alternate floor recall, no other items tested at this time.
|
FIR08-00348
| INSP-Final Inspection | 6/2/2008 | 6/3/2008 | 6/3/2008 12:21:59 PM | A | FAIL |
|
|
Project is not ready for final at this time due to finishes and construction underway-missng escutcheons, paint masking, etc.
|
FIR07-00663
| INSP-Sprinkler Rough-in/Hydro | 6/2/2008 | 6/3/2008 | 6/3/2008 12:20:15 PM | A | PART |
|
|
Overhead hydrostatic testing completed satisfactory for the new system piping.
|
FIR08-00163
| INSP-Sprinkler Rough-in | 6/2/2008 | 6/3/2008 | 6/3/2008 12:19:04 PM | A | PART |
|
|
Remainder of UG fire supply approved for cover including thrust blocks and ductile riser.
|
FIR08-00132
| FIR-Aging Inspection | 6/3/2008 | 6/3/2008 | 6/3/2008 11:53:13 AM | | DONE |
|
|
Work in progress
|
FIR08-00180
| INSP-Final Inspection | 5/30/2008 | 6/3/2008 | 6/2/2008 7:49:04 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 5/30/2008 at 4:48:42 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jun 2 2008 7:49AM.
|