BLD09-00721
| FIRE-Final Inspection | 6/3/2009 | 6/3/2009 | 6/4/2009 3:33:58 PM | P | PASS |
|
|
life safety passed
|
FIR09-00112
| FIR-Aging Inspection | 6/3/2009 | 6/3/2009 | 6/4/2009 10:38:29 AM | | NR |
|
|
Work is in progress
|
FIR09-00239
| INSP-Sprinkler Rough-in/Hydro | 6/2/2009 | 6/3/2009 | 6/3/2009 2:40:14 PM | A | PASS |
|
|
The overhead hydro test passed. All piping can be covered except the pipe just south of the main entrance due to insulation that is hanging from the roof deck acting as an obstruction to the attic sprinklers.
|
BLD09-00568
| FIRE-Final Inspection | 6/2/2009 | 6/3/2009 | 6/3/2009 1:36:09 PM | A | FAIL |
|
|
Repair the two existing exit signs and provide the additional exit sign as shown on the approved plans. All other items are ok. Per Bob Archibald the three thumbturn dead bolts between the warehouse and the showroom/office areas are ok to remain.
|
BLD09-00792
| FIRE-Final Inspection | 6/2/2009 | 6/3/2009 | 6/3/2009 1:24:59 PM | A | PASS |
|
|
Life safety passed. The deadbolt on the rear door was removed as I waited.
|
FIR07-01032
| INSP-Final Inspection | 6/2/2009 | 6/3/2009 | 6/3/2009 9:59:26 AM | A | PASS |
|
|
The sprinklers are complete in the new first floor exit passage way at the skilled nursing area.
|
BLD07-01846
| FIRE-Final Inspection | 6/2/2009 | 6/3/2009 | 6/3/2009 9:58:35 AM | A | FAIL |
|
|
This inspection was for two new entry areas Emergency lighting is required in the exit way. Atleast one fire extinguisher is required as discussed. An exit sign leading to the exit way is missing. The project related fire alarm for this area had issues as well See the city approved fire alarm plans for deficiancies. They include smoke detector and a door holder that are not shown on the plans. A door holder that is shown on the plans but has not been installed. A remote annunciator that has not been installed. A smoke detector that does not set off the general alarm. A room missing a strobe. A wall mount a/v has been revised to a ceiling mount and was the wrong candella. All of these items are in a very small area.
|
FIR08-00382
| INSP-Alarm Testing | 6/3/2009 | 6/3/2009 | 6/3/2009 9:56:02 AM | P | FAIL |
|
|
See the city approved plans for deficiancies. They include smoke detector and a door holder that are not shown on the plans. A door holder that is shown on the plans but has not been installed. A remote annunciator that has not been installed. A smoke detector that does not set off the general alarm. A room missing a strobe. A wall mount a/v has been revised to a ceiling mount and was the wrong candella. All of these items are in a very small area.
|