Inspections for the day of: Friday, June 3, 2011.
Number of inspections: 14
Percentage of inspections complete: 93 %
Percentage of inspections not complete: 7 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC11-00234 General Inspection6/1/20116/1/2011   
ELE11-00314 ELE-Aging Inspection6/3/20116/3/20116/10/2011 2:11:29 PM DONE
see final
ELE11-01137 Electrical Rough-In6/3/20116/3/20116/3/2011 3:25:58 PMPFAIL
please inspect conduit from service to future pad Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman NEC 300.8 electrical and gas piping shall not be in the same raceway or trench
ELE11-01144 Permanent Service6/3/20116/3/20116/3/2011 2:40:45 PMPFAIL
###-#### - katie NEC 230.79 (C) For a one family dwelling the service disconnecting means shall have a rating of an not less than 100 ampere,3 wire. NEC250.56 A single electrode that does not have a resitance of 25 ohms or less shall be augmented by one additional electrode 6 feet apart. Sub-panel in unit 2126 is feed by tri-plex, needsquad-plex for a subpanel. Water pipe bond if incoming water line is metal.
ELE11-01025 Electrical Rough-In6/2/20116/3/20116/3/2011 1:45:24 PMPPART
Jeff Phone #: ###-#### rough-in ok unit 202 unit 301 unit 303 north stairwell for cover
ELE11-00757 Final6/3/20116/3/20116/3/2011 12:22:10 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
ELE11-01130 Rough-In Permanent Service6/3/20116/3/20116/3/2011 11:43:22 AMPPASS
Allan Phone #: ###-#### rough-in p/s u/g n ok
ELE11-01120 Electrical Rough-In6/2/20116/3/20116/3/2011 11:00:13 AMAPASS
Jay Phone #: ###-#### rough-in ok cover counter walls
ELE11-01127 Electrical Rough-In6/2/20116/3/20116/3/2011 10:58:20 AMAPASS
Could we please get this first thing in the morning. Rough in inspection please. Bob Callahan is the contact. Thank you. Phone #: ###-#### >> Inspection requested via web by Laura Longshaw rough-in ok unattached building (mancave)
ELE10-02426 Final6/1/20116/3/20116/3/2011 10:56:40 AMAFAIL
todd Phone #: ###-#### Home owner has moved in, not all receptacles could be tested NEC 210.52 (c) (1) A receptacle outlet shall be install at each wall countertop space that is 12 in. or wider NEC 406.8(B) 15 and 20 ampere 125 and 250 volt receptacles instlled in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. Need to install all lighting fixtures or cap off box, Man doors require a outside fixture for finals
ELE11-00265 Electrical Rough-In6/2/20116/3/20116/3/2011 8:37:01 AMAPASS
Contact Craig Timmons with questions. This is for a ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Vicki Moore rough-in ok cover ceiling grid (basement)
ELE11-01130 Final6/2/20116/3/20116/3/2011 12:00:00 AMACANC
Phone #: ###-#### >> Inspection requested via web by Alan Lusk
ELE11-01133 Temporary Service6/2/20116/3/20116/2/2011 3:47:55 PMAPASS
Phone #: ###-#### >> Inspection requested via web by Dan Rohl t/s u/g ok transformer
ELE11-00869 Electrical Rough-In6/2/20116/3/20116/2/2011 3:16:14 PMAPASS
Above grid ceiling inspection please-Dave Phone #: ###-#### rough-in ok ceiling grid