ESC11-00234
| General Inspection | 6/1/2011 | 6/1/2011 | | | |
|
|
|
ELE11-00314
| ELE-Aging Inspection | 6/3/2011 | 6/3/2011 | 6/10/2011 2:11:29 PM | | DONE |
|
|
see final
|
ELE11-01137
| Electrical Rough-In | 6/3/2011 | 6/3/2011 | 6/3/2011 3:25:58 PM | P | FAIL |
|
|
please inspect conduit from service to future pad Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman NEC 300.8 electrical and gas piping shall not be in the same raceway or trench
|
ELE11-01144
| Permanent Service | 6/3/2011 | 6/3/2011 | 6/3/2011 2:40:45 PM | P | FAIL |
|
|
###-#### - katie NEC 230.79 (C) For a one family dwelling the service disconnecting means shall have a rating of an not less than 100 ampere,3 wire. NEC250.56 A single electrode that does not have a resitance of 25 ohms or less shall be augmented by one additional electrode 6 feet apart. Sub-panel in unit 2126 is feed by tri-plex, needsquad-plex for a subpanel. Water pipe bond if incoming water line is metal.
|
ELE11-01025
| Electrical Rough-In | 6/2/2011 | 6/3/2011 | 6/3/2011 1:45:24 PM | P | PART |
|
|
Jeff Phone #: ###-#### rough-in ok unit 202 unit 301 unit 303 north stairwell for cover
|
ELE11-00757
| Final | 6/3/2011 | 6/3/2011 | 6/3/2011 12:22:10 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
|
ELE11-01130
| Rough-In Permanent Service | 6/3/2011 | 6/3/2011 | 6/3/2011 11:43:22 AM | P | PASS |
|
|
Allan Phone #: ###-#### rough-in p/s u/g n ok
|
ELE11-01120
| Electrical Rough-In | 6/2/2011 | 6/3/2011 | 6/3/2011 11:00:13 AM | A | PASS |
|
|
Jay Phone #: ###-#### rough-in ok cover counter walls
|
ELE11-01127
| Electrical Rough-In | 6/2/2011 | 6/3/2011 | 6/3/2011 10:58:20 AM | A | PASS |
|
|
Could we please get this first thing in the morning. Rough in inspection please. Bob Callahan is the contact. Thank you. Phone #: ###-#### >> Inspection requested via web by Laura Longshaw rough-in ok unattached building (mancave)
|
ELE10-02426
| Final | 6/1/2011 | 6/3/2011 | 6/3/2011 10:56:40 AM | A | FAIL |
|
|
todd Phone #: ###-#### Home owner has moved in, not all receptacles could be tested NEC 210.52 (c) (1) A receptacle outlet shall be install at each wall countertop space that is 12 in. or wider NEC 406.8(B) 15 and 20 ampere 125 and 250 volt receptacles instlled in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. Need to install all lighting fixtures or cap off box, Man doors require a outside fixture for finals
|
ELE11-00265
| Electrical Rough-In | 6/2/2011 | 6/3/2011 | 6/3/2011 8:37:01 AM | A | PASS |
|
|
Contact Craig Timmons with questions. This is for a ceiling inspection. Phone #: ###-#### >> Inspection requested via web by Vicki Moore rough-in ok cover ceiling grid (basement)
|
ELE11-01130
| Final | 6/2/2011 | 6/3/2011 | 6/3/2011 12:00:00 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Alan Lusk
|
ELE11-01133
| Temporary Service | 6/2/2011 | 6/3/2011 | 6/2/2011 3:47:55 PM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Dan Rohl t/s u/g ok transformer
|
ELE11-00869
| Electrical Rough-In | 6/2/2011 | 6/3/2011 | 6/2/2011 3:16:14 PM | A | PASS |
|
|
Above grid ceiling inspection please-Dave Phone #: ###-#### rough-in ok ceiling grid
|