Inspections for the day of: Tuesday, June 3, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02405 ELE-Aging Inspection6/3/20146/3/20146/5/2014 3:14:48 PM DONE
still under construction
ELE10-02823 ELE-Aging Inspection6/3/20146/3/20146/5/2014 2:12:36 PM DONE
still under construction
ELE14-01425 Temporary Service6/3/20146/3/20146/3/2014 3:00:34 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, told contractor shall fix broken 50A receptacle
ELE14-01426 Temporary Service6/3/20146/3/20146/3/2014 2:54:51 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, told contractor to provide breaker blanks
ELE14-01424 Temporary Service6/3/20146/3/20146/3/2014 2:49:53 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn called, told contractor address posted for another street, needs corrected
ELE14-01020 Permanent Service6/3/20146/3/20146/3/2014 2:30:55 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt p/s o/h rec ok
ELE14-01415 Rough-In Permanent Service6/3/20146/3/20146/3/2014 1:42:17 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn ri ok, p/s u/g n ok
ELE14-01355 Electrical Rough-In6/2/20146/3/20146/3/2014 1:07:04 PMPPASS
>> Inspection requested via web by ERIC CENTERS corrections made, ri ok
ELE14-00954 Final6/3/20146/3/20146/3/2014 12:27:12 PMPPASS
Please call ahead for access - Pat Phone #: ###-#### ok final
ELE14-00650 Final6/2/20146/3/20146/3/2014 10:50:19 AMAPASS
Garage code 1979E Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
ELE14-00139 Final6/2/20146/3/20146/3/2014 10:44:07 AMAFAIL
call for code Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left message, left correction notice, NEC 210.8 outside receptacles shall be gfci protected, 406.4 shall securely mount receptacles, garage, down stairs, 404.9 shall install cover plate for switch
ELE14-00771 Conference6/2/20146/3/20146/3/2014 9:44:34 AMADONE
Paul or call ###-#### Phone #: ###-#### met to discuss working space about 5kv controllers for chillers, design is sufficient to allow portable work station to be brought in to work in front of disconnect and contactor, since the power will be disconnected for the controller
ELE14-01277 Rough-In Permanent Service6/2/20146/3/20146/3/2014 8:40:46 AMAPASS
>> Inspection requested via web by Bob Glenn ri ok, p/s u/g n ok
ELE14-00684 Final6/2/20146/3/20146/3/2014 8:21:21 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn ok final
ELE14-01395 Electrical Rough-In6/2/20146/3/20146/2/2014 9:07:16 AMACANC
Kitchen remodel roughin Phone #: ###-#### >> Inspection requested via web by Randy Fletcher Inspection cancelled from web by: Randy Fletcher