Inspections for the day of: Wednesday, June 3, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01625 Temporary Service6/3/20156/3/20156/3/2015 3:35:46 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE15-01633 Electrical Rough-In6/3/20156/3/20156/3/2015 3:25:23 PMPPASS
Under ground rough ok. To verify lperimeter bond distance and receptacle location by pool
ELE15-01633 Final6/3/20156/3/20156/3/2015 3:20:42 PMPFAIL
Fiberglass pool with a 12volt light Phone #: ###-#### Inspection requested via web by cory carman 680.22(A)(1)- At least one receptacle 15 or 20 amp 120 volt GFCI outlet shall be located between 6' and 20' of inside wall of pool.
680.26( B)(2)- Perimeter surface #8 conductor shall be located within 18" to 24" of edge of pool and shall be 4" to 6" below grade.
200.6- Grounded conductor shall be identified full length for conductors smaller than #6.
ELE15-00477 Permanent Service6/3/20156/3/20156/3/2015 2:21:33 PMPFAIL
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.12(A)- unused openings shall be closed. Close main opening not used.
110.24(A)- Service equipment shall be legibly marked in the field with max available fault current. Marking shall include date calculated and be durable to with stand environment.
250.24- Grounding electrode conductor shall be connected to grounded conductor. Unable to verify connection.
ELE15-01593 Final6/3/20156/3/20156/3/2015 1:23:35 PMPPASS
Phone #: ###-#### Inspection requested via web by Thomas wilson Final ok
ELE15-01642 Rough-In Permanent Service6/3/20156/3/20156/3/2015 12:57:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Dan Rohl Rough in ok cover p/s u/g n ok
ELE15-01619 Electrical Rough-In6/2/20156/3/20156/3/2015 10:37:56 AMAPASS
If you have any questions, please call Calvin at ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Basement rec rm and bed lighting to cans. Kitchen remodel rough in ok cover
ELE15-01111 Electrical Rough-In6/3/20156/3/20156/3/2015 10:11:53 AMAPASS
We need an underground inspection for today, site contact is Mike Poff
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Electrical room underground rough in ok cover
ELE15-01099 Electrical Rough-In6/2/20156/3/20156/3/2015 9:40:14 AMAPASS
Randy Phone #: ###-#### Up bathroom phase 1, closet, and kitchen/dining wall. Rough in cover. Check basement for open splice in box
ELE15-01544 Rough-In Permanent Service6/1/20156/3/20156/3/2015 9:09:07 AMAPASS
Cody is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok