ELE15-01625
| Temporary Service | 6/3/2015 | 6/3/2015 | 6/3/2015 3:35:46 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-01633
| Electrical Rough-In | 6/3/2015 | 6/3/2015 | 6/3/2015 3:25:23 PM | P | PASS |
|
|
Under ground rough ok. To verify lperimeter bond distance and receptacle location by pool
|
ELE15-01633
| Final | 6/3/2015 | 6/3/2015 | 6/3/2015 3:20:42 PM | P | FAIL |
|
|
Fiberglass pool with a 12volt light Phone #: ###-#### Inspection requested via web by cory carman 680.22(A)(1)- At least one receptacle 15 or 20 amp 120 volt GFCI outlet shall be located between 6' and 20' of inside wall of pool. 680.26( B)(2)- Perimeter surface #8 conductor shall be located within 18" to 24" of edge of pool and shall be 4" to 6" below grade. 200.6- Grounded conductor shall be identified full length for conductors smaller than #6.
|
ELE15-00477
| Permanent Service | 6/3/2015 | 6/3/2015 | 6/3/2015 2:21:33 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 110.12(A)- unused openings shall be closed. Close main opening not used. 110.24(A)- Service equipment shall be legibly marked in the field with max available fault current. Marking shall include date calculated and be durable to with stand environment. 250.24- Grounding electrode conductor shall be connected to grounded conductor. Unable to verify connection.
|
ELE15-01593
| Final | 6/3/2015 | 6/3/2015 | 6/3/2015 1:23:35 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Thomas wilson Final ok
|
ELE15-01642
| Rough-In Permanent Service | 6/3/2015 | 6/3/2015 | 6/3/2015 12:57:45 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl Rough in ok cover p/s u/g n ok
|
ELE15-01619
| Electrical Rough-In | 6/2/2015 | 6/3/2015 | 6/3/2015 10:37:56 AM | A | PASS |
|
|
If you have any questions, please call Calvin at ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Basement rec rm and bed lighting to cans. Kitchen remodel rough in ok cover
|
ELE15-01111
| Electrical Rough-In | 6/3/2015 | 6/3/2015 | 6/3/2015 10:11:53 AM | A | PASS |
|
|
We need an underground inspection for today, site contact is Mike Poff Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Electrical room underground rough in ok cover
|
ELE15-01099
| Electrical Rough-In | 6/2/2015 | 6/3/2015 | 6/3/2015 9:40:14 AM | A | PASS |
|
|
Randy Phone #: ###-#### Up bathroom phase 1, closet, and kitchen/dining wall. Rough in cover. Check basement for open splice in box
|
ELE15-01544
| Rough-In Permanent Service | 6/1/2015 | 6/3/2015 | 6/3/2015 9:09:07 AM | A | PASS |
|
|
Cody is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
|