ELE18-02369
| Final | 6/3/2019 | 6/3/2019 | 6/3/2019 4:05:16 PM | P | FAIL |
|
|
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell 110.22- Each roof top unit shall be identified as per which disconnecting means operates it. 314.20= Boxes that are not flush with combustible materials shall be extented to be flush. All receptacles in electrical room on all floors.
|
ELE18-04449
| Final | 6/3/2019 | 6/3/2019 | 6/3/2019 3:35:42 PM | P | FAIL |
|
|
Call Jay for access ###-#### Phone #: ###-#### Inspection requested via web by jamie berg 2 open light boxes, 1 in up game room and 1 in up hall closet above door. Rest checked ok
|
ELE19-00808
| Final | 6/3/2019 | 6/3/2019 | 6/3/2019 2:26:58 PM | P | PASS |
|
|
Garage code 3283 Phone #: ###-#### Inspection requested via web by William Andrews Final ok
|
ELE19-01489
| Electrical Rough-In | 5/31/2019 | 6/3/2019 | 6/3/2019 1:30:16 PM | P | PASS |
|
|
Von. Underground. Please call prior to heading to the site. Phone #: ###-#### Inspection requested via web by Sean DeLacy 2nd concrete encased electrode added to north side of elec. rm OK. Conduit ran over to underground metal water pipe. Electrical room and kitchen underground only rough in ok cover.
|
ELE19-01662
| Final | 5/31/2019 | 6/3/2019 | 6/3/2019 12:14:53 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by brian morrow 210.71- Conference or meeting rooms 215 sq.ft. and larger shall have a floor receptacle installed. 281 sq.ft. rm. Minimum required receptacles in a conference room, layout as if residential living space, minimum can be located where ever wanted as long as min number is present. 6 min needed.
|
ELE19-01995
| Final | 5/31/2019 | 6/3/2019 | 6/3/2019 10:17:45 AM | A | PASS |
|
|
Please call Brodie with any questions Phone #: ###-#### Inspection requested via web by William Salts Final ok
|
ELE19-01995
| Electrical Rough-In | 6/3/2019 | 6/3/2019 | 6/3/2019 10:17:19 AM | P | PASS |
|
|
Please call Brodie with any questions Phone #: ###-#### Inspection requested via web by William Salts Non metallic conduit on ceiling to receptacle for gas heaters rough in ok
|
ELE19-01018
| Permanent Service | 5/31/2019 | 6/3/2019 | 6/3/2019 9:58:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack p/s u/g n ok
|
ELE19-01634
| Electrical Rough-In | 6/3/2019 | 6/3/2019 | 6/3/2019 9:30:58 AM | A | PASS |
|
|
trench inspection Phone #: ###-#### Inspection requested via web by steve sellers Under ground to detached garage roug in ok cover
|
ELE19-00784
| Permanent Service | 5/30/2019 | 6/3/2019 | 6/3/2019 9:19:23 AM | A | PASS |
|
|
had to fix service wires Phone #: ###-#### Inspection requested via web by kevin blackmon p/s u/g n ok
|
ELE19-01057
| Final | 5/31/2019 | 6/3/2019 | 6/3/2019 9:03:57 AM | A | PASS |
|
|
Call Ryan for lock box code Phone #: ###-#### Inspection requested via web by Ryan Schaffer Final ok
|