Inspections for the day of: Monday, June 3, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02369 Final6/3/20196/3/20196/3/2019 4:05:16 PMPFAIL
Call Joey Campbell prior to arrival. Phone #: ###-#### Inspection requested via web by Scott Campbell
110.22- Each roof top unit shall be identified as per which disconnecting means operates it.
314.20= Boxes that are not flush with combustible materials shall be extented to be flush. All receptacles in electrical room on all floors.
ELE18-04449 Final6/3/20196/3/20196/3/2019 3:35:42 PMPFAIL
Call Jay for access ###-#### Phone #: ###-#### Inspection requested via web by jamie berg
2 open light boxes, 1 in up game room and 1 in up hall closet above door. Rest checked ok
ELE19-00808 Final6/3/20196/3/20196/3/2019 2:26:58 PMPPASS
Garage code 3283 Phone #: ###-#### Inspection requested via web by William Andrews Final ok
ELE19-01489 Electrical Rough-In5/31/20196/3/20196/3/2019 1:30:16 PMPPASS
Von. Underground. Please call prior to heading to the site. Phone #: ###-#### Inspection requested via web by Sean DeLacy

2nd concrete encased electrode added to north side of elec. rm OK. Conduit ran over to underground metal water pipe. Electrical room and kitchen underground only rough in ok cover.
ELE19-01662 Final5/31/20196/3/20196/3/2019 12:14:53 PMAFAIL
Phone #: ###-#### Inspection requested via web by brian morrow
210.71- Conference or meeting rooms 215 sq.ft. and larger shall have a floor receptacle installed. 281 sq.ft. rm.
Minimum required receptacles in a conference room, layout as if residential living space, minimum can be located where ever wanted as long as min number is present. 6 min needed.
ELE19-01995 Final5/31/20196/3/20196/3/2019 10:17:45 AMAPASS
Please call Brodie with any questions Phone #: ###-#### Inspection requested via web by William Salts Final ok
ELE19-01995 Electrical Rough-In6/3/20196/3/20196/3/2019 10:17:19 AMPPASS
Please call Brodie with any questions Phone #: ###-#### Inspection requested via web by William Salts
Non metallic conduit on ceiling to receptacle for gas heaters rough in ok
ELE19-01018 Permanent Service5/31/20196/3/20196/3/2019 9:58:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Lee VanSchoiack
p/s u/g n ok
ELE19-01634 Electrical Rough-In6/3/20196/3/20196/3/2019 9:30:58 AMAPASS
trench inspection Phone #: ###-#### Inspection requested via web by steve sellers
Under ground to detached garage roug in ok cover
ELE19-00784 Permanent Service5/30/20196/3/20196/3/2019 9:19:23 AMAPASS
had to fix service wires Phone #: ###-#### Inspection requested via web by kevin blackmon p/s u/g n ok
ELE19-01057 Final5/31/20196/3/20196/3/2019 9:03:57 AMAPASS
Call Ryan for lock box code Phone #: ###-#### Inspection requested via web by Ryan Schaffer Final ok