Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR20-00148 INSP-Sprinkler Rough-in/Hydro6/3/20206/3/20206/3/2020 3:04:07 PMPCANC
Cancelled per conversation with point of contact due too pressure loss, hydro will be rescheduled for a later date.

Mike Martin is contact-Underground Hydro Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00743 INSP-Sprinkler Rough-in/Hydro6/3/20206/3/20206/3/2020 2:17:20 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.

Contact Tanner Loomis ###-#### 30 Min prior to Hyrdo Insp start please

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
FIR19-00743 INSP-Sprinkler Rough-in/Hydro6/2/20206/3/20206/3/2020 2:16:34 PMACANC
Contact Tanner Loomis ###-#### 30 Min prior to Hydro Insp start please
Tanner is requesting a 9 AM Insp time please.

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD18-04071 FIRE-Final Inspection6/2/20206/3/20206/3/2020 2:16:22 PMPPASS
No fire sprinklers, no fire aalrms, fire extinguishers are placed with current inspection tags. Final inspection for life fire safety complete, signature provided on permit sign off card.

Phone #: ###-#### Inspection requested via web by chad stradley
FIR20-00148 INSP-Supply line flush6/3/20206/3/20206/3/2020 11:54:49 AMPDONE
Underground main line flush witnessed.

Mike Martin is contact Phone #: ###-#### Inspection requested via web by jeremiah robison
FIR19-00743 INSP-Final Inspection6/2/20206/3/20206/3/2020 10:37:25 AMAFAIL
23MAR2020 inspection notes stated some classroom walls went all the way to the deck, upright coverage was adjusted/added for extension of walls, city approved drawings need to be updated showing added haeds.

Contact Tanner Loomis ###-#### 20 min prior to Final Insp start please.
Tanner would like to final after Hydro Insp sched for AM 6/3

Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
BLD19-04590 FIRE-Final Inspection6/2/20206/3/20206/3/2020 10:35:43 AMAFAIL
Provide single action door hardware on doors that did not unlock upon handle action. Provide correct signage on main entry reading "Door to remain unliocked whilke building is occupied". Service or replace non-functioning exit signs, west side of tenant space.

call ahead 30 minutes - screened // August Phone #: ###-####
BLD19-03618 FIRE-Final Inspection6/1/20206/3/20206/2/2020 9:21:10 AMACANC
Rescheduled for 04JUN2020 to coincide with fire alarm inspection, this request is cancelled.

Bruce *screeend* Phone #: ###-####