Inspections for the day of: Monday, June 30, 2003.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR00-00538 FIR-Aging Inspection6/30/20036/30/20036/30/2003 12:00:00 AM PASS
BLD03-00759 FIRE-Final Inspection6/27/20036/30/20036/30/2003 12:00:00 AMAFAIL
###-#### The map for the facp that was provided did not match what has been installed and did not include device addresses 6/30/2003 11:14:02 AM
FIR03-00117 INSP-Final Inspection6/26/20036/30/20036/30/2003 12:00:00 AMPFAIL
The inspectors test orfices in Hancocks Fabrics and the Post Office still do not have the correct orfice installed in the inspectors test lines. Still need test papers 6/30/2003 3:43:07 PM
FIR02-00432 INSP-Final Inspection6/30/20036/30/20036/30/2003 12:00:00 AMPFAIL
Install wiring connections in devices or boxes per NFPA 70 for all fire alarm devices 6/30/2003 3:04:39 PM