ELE05-01909
| Electrical Rough-In | 6/30/2005 | 6/30/2005 | 6/30/2005 4:17:07 PM | P | PASS |
|
|
james-- for the ceiling ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ceiling only ok to cover
|
ELE05-00336
| Final | 6/30/2005 | 6/30/2005 | 6/30/2005 4:11:45 PM | P | PASS |
|
|
HAD TO PULL A PERMIT TO GET AN INSPECTION SO WE COULD LET THE HOME SELLER KNOW WHAT NEEDED TO BE BROUGHT UP TO CODE..WE NEVER ENDED UP DOING ANY WORK.; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok to final
|
ELE05-00760
| Final | 6/29/2005 | 6/30/2005 | 6/30/2005 2:35:30 PM | P | FAIL |
|
|
alan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice,408.4 ckt directory shall be specific,422.30 disc shall be supplied for water heater, BCC4-05-33 and 110.2 water heater shall be listed.
|
ELE05-02328
| Rough-In Permanent Service | 6/30/2005 | 6/30/2005 | 6/30/2005 12:38:25 PM | P | NH |
|
|
dan ###-#### they will recall
|
ELE05-01018
| Final | 6/30/2005 | 6/30/2005 | 6/30/2005 12:35:18 PM | P | PASS |
|
|
INSPECTION HAPPENED WITH FINAL OF BUILDING..NEED TO CLOSE OUT THIS PERMIT.; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok to final
|
ELE05-02325
| Permanent Service | 6/30/2005 | 6/30/2005 | 6/30/2005 12:10:39 PM | P | PASS |
|
|
chuck; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s u/g exst ok
|
ELE05-01619
| Final | 6/29/2005 | 6/30/2005 | 6/30/2005 9:52:37 AM | A | FAIL |
|
|
Call prior to inspection Internet Inspection Request from: Steve Craig called ncontr, left corr notice, 406.4 recpts shall be securely fastened, 408.4 circuit directory shall be provided for sub-panel, 110.2 boiler and steamer shall be listed
|
ELE05-01560
| Final | 6/29/2005 | 6/30/2005 | 6/30/2005 9:11:02 AM | A | FAIL |
|
|
Call Rob if this fails at ###-####; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL called contr, left corr notice, 406.5,404.9 faceplates shall cover openings and seat against mounting surface,408.4 circuit directory shall be specific, 110.26(A)(2) panel shall have 30" wide work space, 422.16(B)(1)(2) disposal cord shall be max 3' long,210.8(A)(3) outdoor recpts shall be gfci, 314.21 sheetrock shall be repaired in util room for light, 210.70(A)(2)(a) light shall be in stairway
|
ELE05-01559
| Final | 6/29/2005 | 6/30/2005 | 6/30/2005 9:01:34 AM | A | FAIL |
|
|
Call Rob if this fails at ###-####; Phone #: ###-#### Internet Inspection Request from: KATHY WEIL called contr, left corr notice, 352.30(A) rnc shall be fastened within 3' of box,406.5,404.9 faceplates shall cover openings and seat against mounting surface, 110.26(A)(2) panel shall have 30" wide work space,210.8(A)(3) outdoor recpts shall have gfci, 422.16(A) disposal cord connector shall be tight,210.70(A)(2) light shall be in stairway, 408.4 circuit directory shall be specific
|