ELE06-02390
| Temporary Service | 6/30/2006 | 6/30/2006 | 6/30/2006 4:18:26 PM | P | PASS |
|
|
linda; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s u/g n ok
|
ELE06-00256
| Final | 6/30/2006 | 6/30/2006 | 6/30/2006 4:06:24 PM | P | CANC |
|
|
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, floor contractor won't allow access until 7-1-06
|
ELE06-02452
| Electrical Rough-In | 6/30/2006 | 6/30/2006 | 6/30/2006 3:26:30 PM | P | PASS |
|
|
lloyd; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok
|
ELE06-02360
| Rough-In Permanent Service | 6/29/2006 | 6/30/2006 | 6/30/2006 2:51:16 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange ric ok, p/s u/g n ok
|
ELE06-01265
| Final | 6/30/2006 | 6/30/2006 | 6/30/2006 2:16:44 PM | P | NH |
|
|
michael; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called and told owner he should recall when we can get in
|
ELE06-00511
| Final | 6/30/2006 | 6/30/2006 | 6/30/2006 1:28:02 PM | P | PART |
|
|
any questions call jim ###-#### signed t/o card, open items are elevator and office partitions
|
ELE06-01972
| Electrical Rough-In | 6/30/2006 | 6/30/2006 | 6/30/2006 12:49:48 PM | P | PASS |
|
|
Ceiling cover, please contact Dan Wilken, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok to cover ceiling
|
ELE06-02419
| Electrical Rough-In | 6/29/2006 | 6/30/2006 | 6/30/2006 12:06:21 PM | A | PART |
|
|
ceiling; Phone #: ###-#### Internet Inspection Request from: Jim Williams needs to get lv cleaned up, rest ok
|
ELE06-02417
| Electrical Rough-In | 6/29/2006 | 6/30/2006 | 6/30/2006 10:50:19 AM | A | PART |
|
|
ceiling; Phone #: ###-#### Internet Inspection Request from: Jim Williams told elect to fix lv wiring. rest ok. will recall
|
ELE06-00608
| Final | 6/29/2006 | 6/30/2006 | 6/30/2006 10:36:02 AM | A | FAIL |
|
|
n/a; Phone #: ###-#### Internet Inspection Request from: TJ Sturges called, left message, left corr notice, nec 440.4 a/c shall be marked to allow max disc rating to be determined, 4314.21 drywall shall be patched at front door switch, 110.3(B) listed equip shall be installed according to mfg instructions- fan globe, mbr, jetted tub access min 15"x20", 210.52(A)(1) recpts shall be provided in wall space at desk top of stairs,BCC all equip shall be installed,disposal Note, check recpt operation in media closet
|
ELE06-02309
| Electrical Rough-In | 6/29/2006 | 6/30/2006 | 6/30/2006 9:56:16 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ric ok, p/s u/g n ok
|
ELE06-02312
| Rough-In Permanent Service | 6/28/2006 | 6/30/2006 | 6/30/2006 8:55:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/28/2006 at 6:45:25 AM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE06-01465
| Final | 6/29/2006 | 6/30/2006 | 6/30/2006 8:27:01 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 6/29/2006 at 10:43:31 AM. Contact: ###-####. called, left message, left survey, nec 406.5 recpt faceplates shall seat against mounting surface,406.4(B) recpts shall be held rigidly against box
|
ELE06-02360
| Rough-In Permanent Service | 6/23/2006 | 6/30/2006 | 6/29/2006 11:14:36 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange Inspection cancelled from web by: Daryl DeGrange
|