FIR06-00159
| INSP-Final Inspection | 6/29/2006 | 6/30/2006 | 6/30/2006 4:27:39 PM | A | FAIL |
|
|
One duct detector at first floor north plan FP2 failed to function, shunt trip for the elevator failed to operate, method to test the HD in the elevator control room not provided, need to remove cover at the sd above nac panel northeast side, security door is still not installed at the main entry exit.
|
FIR06-00128
| INSP-Final Inspection | 6/30/2006 | 6/30/2006 | 6/30/2006 4:21:30 PM | P | PASS |
|
|
Final fire sprinkler inspection passed, required corrections have been made, permit finaled.
|
BLD06-01235
| FIRE-Final Inspection | 6/30/2006 | 6/30/2006 | 6/30/2006 2:30:31 PM | P | NR |
|
|
The project related fire alarm permit must be requested for inspection and final prior to life safety final approval.
|
FIR06-00444
| INSP-Sprinkler Rough-in | 6/30/2006 | 6/30/2006 | 6/30/2006 2:28:30 PM | P | PART |
|
|
UG supply line and riser stub are good for cover, need to provide method for seismic clearance at the ductile riser where pipe will pass through floor slab.
|
FIR05-00713
| INSP-Final Inspection | 6/29/2006 | 6/30/2006 | 6/30/2006 1:54:07 PM | P | FAIL |
|
|
Several items need correction, project is not ready for final inspection at this time. Preliminary rough-in inspection completed today addressing items such as incorrect hangers, spacing, head temps, seismic bracing and clearance, riser and plans which do not match installation- See 10 item correction notice left on site for review of a partial list of defficiencies. C/N does not constitute a complete listing of all issues regarding fire sprinklers at this time.
|
FIR06-00250
| INSP-Final Inspection | 6/28/2006 | 6/30/2006 | 6/30/2006 12:07:22 PM | A | PASS |
|
|
Fire alarm work passed field inspection, permit finaled.
|
FIR06-00293
| INSP-Final Inspection | 6/27/2006 | 6/30/2006 | 6/30/2006 12:06:37 PM | A | PASS |
|
|
Fire sprinkler permit passed final inspection.
|
FIR05-00883
| INSP-Supply line flush | 6/29/2006 | 6/30/2006 | 6/30/2006 11:27:05 AM | A | PART |
|
|
UG supply line flush performed satisfactory.
|
FIR05-00425
| INSP-Sprinkler Rough-in/Hydro | 6/29/2006 | 6/30/2006 | 6/30/2006 9:33:19 AM | A | PART |
|
|
OH rough-in for the 11th floor is acceptable for cover at the hard lid areas.
|
FIR06-00444
| INSP-Sprinkler Rough-in | 6/29/2006 | 6/30/2006 | 6/30/2006 12:00:00 AM | A | CANC |
|
|
Please call 1 hour prior to inspection. UG to cover.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|