Inspections for the day of: Friday, June 30, 2006.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00161 FIR-Aging Inspection6/30/20066/30/20067/5/2006 2:02:47 PM NR
work is in progress
BLD06-00485 FIRE-Final Inspection6/29/20066/30/20066/30/2006 5:04:57 PMPFAIL
provide approved hardware on door to hvac closet
FIR05-00644 INSP-Sprinkler Rough-in6/29/20066/30/20066/30/2006 5:04:24 PMPPART
Rough-in for the pool/clubhouse area is mostley passed. See approved plans for areas needing corrections. Branchlines have been added in areas not provided with protection. As-builts will need to be provided prior to cover. Combustible pockets still need protection. Branchlines in peak are too far down from the peak
FIR05-00827 INSP-Final Inspection6/29/20066/30/20066/30/2006 5:01:36 PMACANC
mike; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
BLD05-02815 FIRE-Final Inspection6/29/20066/30/20066/30/2006 1:23:24 PMAFAIL
Provide address for the apartments at the bottom door and at each of the doors into the individual apartments. Also mount the fire extinguisher as noted in the review comments and provide with an annual inspection.
BLD05-02192 FIRE-Final Inspection6/29/20066/30/20066/30/2006 11:53:20 AMAFAIL
See fire dept. review comments for items marked that need addressing. Items include signage at property entrances, removing the manual flush bolts on two interior doors, providing address, providing occupant load sign, relocate and test duct smoke detectors (or remove if allowed) and install fencing and gate hardware around the pool. Per review comments a separate permit is required for the swimming pool.
BLD05-02854 FIRE-Final Inspection6/30/20066/30/20066/30/2006 10:54:01 AMPPASS
Life safety finaled
FIR06-00470 INSP-Sprinkler Rough-in6/29/20066/30/20066/30/2006 9:43:05 AMAPASS
permit finaled